Yokogawa EJX930A User Manual
Page 68
<9. Parameter Lists>
9-4
IM 01C25R03-01E
Relative
Index Index
Parameter Name
Factory Default
Write
Mode
Explanation
23
2023 SENSOR_CAL_
METHOD
103: factory
trim standard
calibration
O/S
The method of the last sensor calibration.
100=volumetric
101=static weight
102=dynamic weight
103=factory trim standard calibration
104=user trim standard calibration
105=factory trim special calibration
106=user trim special calibration
255=others
24
2024 SENSOR_CAL_LOC
—
O/S
Set/indicate the location of the last sensor calibration.
25
2025 SENSOR_CAL_DATE —
O/S
Set/indicate the date of the last sensor calibration.
26
2026 SENSOR_CAL_WHO —
O/S
Set/indicate the name of the person responsible for the last
sensor calibration.
27
2027 SENSOR_ISOLATOR_
MTL
Unkown
—
Defines the construction material of the isolating diaphragms.
28
2028 SENSOR_FILL_FLUID Unkown
—
Defines the type of fluid used in the sensor.
29
2029 SECONDARY_VALUE
—
Static pressure (high pressure side) value and status.
30
2030 SECONDARY_
VALUE_UNIT
1545 (MPaa)
—
The engineering unit of static pressure (high pressure side).
This unit is linked to XD_SCALE.unit of AI blocks.
31
2031 CAL_DEVIATION_HI
0
O/S
Deviation value for span adjustment.
32
2032 CAL_DEVIATION_LO 0
O/S
Deviation value for zero adjustment.
33
2033 EXTERNAL_ZERO_
TRIM
0
O/S
Permission of external zero-adjustment.
34
2034 PRIMARY_VALUE_
FTIME
2
O/S
Damping time constant for primary value.
35
2035 TERTIARY_VALUE
—
Value and status of static pressure at low side.
36
2036 SP_VALUE_TYPE
109 (absolute
pressure)
O/S
Select the type of measurement for static pressure, absolute or
gauge.
37
2037 SP_VALUE_RANGE
Range of capsule —
High and low range limit values, engineering units, and decimal
point place for static pressure.
38
2038 CAL_SP_POINT_HI
25
O/S
The highest calibrated value for static pressure.
39
2039 CAL_SP_POINT_LO
0
O/S
The Lowest calibrated value for static pressure.
40
2040 CAL_SP_MIN_SPAN
1.0
—
The minimum calibration span allowed for static pressure.
41
2041 CAL_SP_UNIT
1545 (MPaa)
—
The calibrated engineering unit for static pressure. This unit is
linked to XD_SCALE.unit of AI blocks.
42
2042 CAL_SP_DEVIATION_
HI
0
O/S
Deviation value for span adjustment of static pressure.
43
2043 CAL_SP_DEVIATION_
LO
0
O/S
Deviation value for zero adjustment of static pressure.
44
2044 SP_VALUE_FTIME
1
O/S
Damping time constant for static pressure.
45
2045 ATM_PRESS
101.325
O/S
Atmosphere pressure value used to obtain gauge pressure
value from absolute pressure.
46
2046 CURRENT_ATM_
PRESS_ENABLE
0
O/S
Automatically sets the L-side static pressure value to the
atmospheric pressure value (ATM_PRESS).
47
2047 EXT_TEMP_VAL
—
Indicates the external temperature value and status.
48
2048 EXT_TEMP_RANGE
-200 to 850°C
—
Indicates the external temperature sensor range, unit and
decimal point.
49
2049 CAL_EXT_TEMP_
POINT_HI
100
O/S
This is High-side adjustment value. Adjust this value so that the
current external temperature becomes this setting value.
50
2050 CAL_EXT_TEMP_
POINT_LO
0
O/S
This is Low-side adjustment value. Adjust this value so that the
current external temperature becomes this setting value.
51
2051 CAL_EXT_TEMP_
MIN_SPAN
10.0
—
Indicates the minimum span of the external temperature.
52
2052 CAL_EXT_TEMP_
UNIT
1001
—
Indicates the calibration unit of the external temperature sensor.
53
2053 CAL_EXT_TEMP_
DEVIATION_HI
0
O/S
This is the adjustment coefficient for performing span
adjustment of the external temperature.
54
2054 CAL_EXT_TEMP_
DEVIATION_LO
0
O/S
This is the adjustment coefficient for performing zero adjustment
of the external temperature.
55
2055 EXT_TEMP_VALUE_
FTIME
1.0
O/S
Sets the primary filter time constant (unit: seconds) of the
external temperature.
56
2056 EXT_TEMP_OPTS
0
O/S
Selects the external temperature selection operation.
0=No Selection OFF (output of external temperature)
1=Yes Selection ON (output of FIXED_EXT_TEMP_VALUE)
2=Fall Back Selection at broken wire (output of FIXED_EXT_
TEMP_VALUE at broken wire)