2 sensor transducer block, Sensor transducer block -3 – Yokogawa EJX930A User Manual
Page 67
<9. Parameter Lists>
9-3
IM 01C25R03-01E
Relative
Index Index
Parameter Name
Factory Default
Write
Mode
Explanation
56
1056 SOFTDWN_ACT_
AREA
0
—
Indicates the ROM number of the currently working FlashROM.
0: FlashROM #0 working
1: FlashROM #1 working
57
1057 SOFTDWN_MOD_
REV
1, 0, 0, 0, 0, 0, 0,
0, 0
–
Indicates the software module revision.
58
1058 SOFTDWN_ERROR
0
–
Indicates the error during a software download.
Refer Table A7.4.
9.2 SENSOR Transducer Block
Relative
Index Index
Parameter Name
Factory Default
Write
Mode
Explanation
0
2000 Block Header
TAG: “STB”
Block
Tag=O/S
Information on this block such as Block Tag, DD Revision,
Execution Time etc.
1
2001 ST_REV
—
—
The revision level of the static data associated with the function
block. The revision value will be incremented each time a static
parameter value in the block is changed.
2
2002 TAG_DESC
Null
AUTO
The user description of the intended application of the block.
3
2003 STRATEGY
1
AUTO
The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
4
2004 ALERT_KEY
1
AUTO
The identification number of the plant unit. This information may
be used in the host for sorting alarms, etc.
5
2005 MODE_BLK
AUTO
AUTO
The actual, target, permitted, and normal modes of the block.
6
2006 BLOCK_ERR
—
—
This parameter reflects the error status associated with
hardware or software components associated with a block. It is
a bit string, so that multiple errors may be shown.
7
2007 UPDATE_EVT
—
—
This alert is generated by any change to the static data.
8
2008 BLOCK_ALM
—
—
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the Active status in the Status attribute.
9
2009 TRANSDUCER_
DIRECTORY
—
—
A directory that specifies the number and starting indices of the
transducers.
10
2010 TRANSDUCER_TYPE 100 (Standard
Pressure with
Calibration)
—
Identifies transducer.
11
2011 XD_ERROR
—
—
The error code in transducer.
0=No failure
18=Calibration error
20=Electronics failure
22=I/O failure
12
2012 COLLECTION_
DIRECTORY
—
—
A directory that specifies the number, starting indices, and DD
Item Ids of the data collections in each transducer within a
transducer block.
13
2013 PRIMARY_VALUE_
TYPE
107: differential
pressure
O/S
The type of measurement represented by primary value.
14
2014 PRIMARY_VALUE
—
—
The measured value and status available to the function block.
15
2015 PRIMARY_VALUE_
RANGE
Range of capsule —
The High and Low range limit values, engineering units code
and the number of digits to the right of the decimal point to be
used to display the primary value.
16
2016 CAL_POINT_HI
Max range
O/S
The highest calibrated value.
17
2017 CAL_POINT_LO
0
O/S
The lowest calibrated value.
18
2018 CAL_MIN_SPAN
Minimum span of
capsule
—
The minimum calibration span value allowed.
19
2019 CAL_UNIT
kPa
—
The engineering unit for the calibrated values.
20
2020 SENSOR_TYPE
Silicon resonant
—
The type of sensor.
21
2021 SENSOR_RANGE
Range of capsule —
The High and Low range limit values, engineering units code
and the number of digits to the right of the decimal point for the
sensor.
22
2022 SENSOR_SN
Serial No.
—
Serial number.