<4. Getting Started>
4-3
IM 01C25R03-01E
4.3 Bus Power ON
Turn on the power of the host and the bus. Where
the EJX multivariable transmitter is equipped with
an LCD indicator, first all segments are lit, then the
display begins to operate. If the indicator is not lit,
check the polarity of the power supply.
Using the host device display function, check that
the EJX multivariable transmitter is in operation on
the bus.
The device information, including PD tag, Node
address, and Device ID, is described on the sheet
attached to the device. The device information is
given in duplicate on this sheet.
DEVICE INFORMATION
Device ID
:
594543000EXXXXXXXX
PD Tag
:
FT1001
Device Revision
:
1
Node Address
:
0xf5
Serial No.
:
XXXXXXXXXXXXXXXXX
Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld/ (English) or
http://www.yokogawa.co.jp/fld/ (Japanese)
DEVICE INFORMATION
Device ID
:
594543000EXXXXXXXX
PD Tag
:
FT1001
Device Revision
:
1
Node Address
:
0xf5
Serial No.
:
XXXXXXXXXXXXXXXXX
Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld/ (English) or
http://www.yokogawa.co.jp/fld/ (Japanese)
F0403.ai
Figure 4.4
Device Information Sheet Attached to
EJX
If no EJX multivariable transmitter is detected,
check the available address range and the polarity
of the power supply. If the node address and PD
tag are not specified when ordering, default value
(0xF5) is factory set. If two or more devices are
connected at a time with default value, only one
device will detected from the host keep the default
address and the others’ address will become
default address of 0xF8 or later. Separately connect
each device and set a different address for each.
4.4 Integration of DD
If the host supports DD (Device Description), the
DD of the EJX multivariable transmitter needs to be
installed. Check if host has the following directory
under its default DD directory.
594543\000E
(594543 is the manufacturer number of
Yokogawa Electric Corporation, and 000E is the
EJX multivariable transmitter device number,
respectively.)
If this directory is not found, the DD of the EJX910A
has not been included. Create the above directory
and copy the DD file (0m0n.ffo, 0m0n.sym) (m, n is
a numeral) into the directory. "0m" in the file name
shows the device revision, and "0n" shows the DD
revision. If you do not have the DD or capabilities
files, you can download them from our web site:
http://www.yokogawa.com/fld/
Once the DD is installed in the directory, the
name and attribute of all parameters of the EJX
multivariable transmitter are displayed.
Off-line configuration is possible by using
capabilities files.
EJX has two capabilities levels, "1" and "2".
Select "Capabilities level = 1" when the EJX don't
have LC1(PID function) option.
Select "Capabilities level = 2" when the EJX has
LC1(PID function) option.
The capabilities level defines the kind and the
number of function blocks that can be used.
The table below shows the relation.
The relation between and function blocks that can
be used
Capabilities
Level
AI
SC
IT
IS
AR PID
1
5
1
1
1
1
0
2
5
1
1
1
1
1