Input 2 wiring, Input 2, Digital event – Watlow Series 96 User Manual
Page 9: Figure 3.3a, Figure 3.3b, Figure 3.3c
Wa t l o w S e r i e s 9 6
W i r i n g
■
3 . 3
ç
WARNING:
To avoid damage to
property and equipment,
and/or injury of loss of
life, use National Electric
Code (NEC) standard
wiring practices to install
and operate the Series
96. Failure to do so could
result in injury or death.
ç
CAUTION:
Maintain isolation
between input 1 and
input 2 to prevent a
ground loop. A ground
loop may cause incorrect
readings, dashes across
the upper display or the
display of error codes.
Failure to follow this
guideline could result in
damage to equipment
and product.
ç
**CAUTION:
Process input does not
have sensor break
protection. Outputs can
remain full on.
Input 2 Wiring
Figure 3.3a –
**
0-5VÎ, 1-5VÎ or 0-10VÎ (dc) Process
Universal signal conditioner
96 _ 1 - _ _ _ _ - _ _ _ _
Input impedance: 20k
Ω
Figure 3.3b –
**
0-20mA or 4-20mA Process
Universal signal conditioner
96 _ 1 - _ _ _ _ - _ _ _ _
Input impedance: 100
Ω
Figure 3.3c –
Digital Event
96 _ 1 - _ _ _ _ - _ _ _ _
Voltage input
3-36VÎ (dc) Event Input High State
0-2VÎ (dc) Event Input Low State
Contact closure
0-2k
Ω
Event Input Low State
> 23k
Ω
Event Input High State
10
8
1
2
3
4
5
6
7
13 14 15
11
12
16 17 18
19 20 21
9
3
1
+
-
2.67k
Ω
EVENT
+
3
EVENT
-
1
20k
Ω
100
Ω
+5V
Internal Circuitry
10
8
1
2
3
4
5
6
7
13 14 15
11
12
16 17 18
19 20 21
9
1
2
+
-
10
8
1
2
3
4
5
6
7
13 14 15
11
12
16 17 18
19 20 21
9
1
3
-
+