Chapter six, Chapter 6: parameters, Chapter six parameters – Watlow Series 96 User Manual
Page 31: Home page
Wa t l o w S e r i e s 9 6
P a r a m e t e r s
■
6 . 1
Chapter Six
Parameters
6
Home Page
The resting-state display shows one of the following sets of data, depending on controller
setup. The first prompt appears in the top display, the second in the bottom.
The parameters selected in the Custom Menu (Factory Page) will appear here.
Active: Always
Active if Auto-Manual Operation
Mode (User Menu) is set to
[man] (manual), or if there is
an error.
100 r
310 r/w
Range Low 1 to Range
High 1
heat modes: 0.0 to 100.0
cool modes: -100.0 to 0.0
heat/cool modes:
-100.0 to 100.0
[``96]
Process 1
[`5)0] Manual Set Point**
Monitor the Process
1 value and change
manual set point
value.
Active: Always
Active if Event Function
[E`Fn]
(Input 2 Menu) is set to
[``SP]
(event set point), an event con-
dition exists and Auto-Manual
Operation Mode (User Menu) is
set to
[auto] (automatic).
100 r
202 r
Range Low 1 to Range
High 1
[``96]
Process 1
[`5)0] Event Set Point**
Monitor the Process
1 value and Event
Set Point values.
Active: Always
Active if the remote set point is
active and Local or Remote
Mode
[`L-R] (User Menu) is
set to
[```R] (remote) and
Auto-Manual Operation Mode
(User Menu) is set to
[auto]
(automatic).
100 r
202 r
Range Low 1 to Range
High 1
[``96]
Process 1
[`200] Remote Set
Point**
Monitor the Process
1 value and Remote
Set Point values.
Active: Always
Active if the event set point is not
active and Local or Remote
Mode (User Menu) is set to
[```l] (local) or Auto-Manual
Operation Mode (User Menu) is
set to
[auto] (automatic).
[`OFF] will appear when slewing
below the
[rl`1]] value.
100 r
300 r/w
Range Low 1 to Range
High 1
[`OFF] Off
[``96]
Process 1
[`100] Set Point 1
Monitor the Process
1 value and change
the Set Point values.
Display
Parameter
Range
Default
Modbus
Conditions for
(Modbus Value)
Register
Parameters to Appear
read/write
*These parameters are added if the ramping software option has been ordered (96 _ _ - _ _ _ _ - AA _ _ ) .
**These parameters are removed if the ramping software option has been ordered (96 _ _ - _ _ _ _ - AA _ _ ) .
NOTE: Refer to Chapter 7 of this manual for information on parameters for creating ramp and soak profiles in Ramping
versions of the Series 96.
NOTE: To see how all the pages, menus and parameters are grouped, refer to the inside back cover of this manual.
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.
Home Page