Operations page / pid 2 menu – Watlow Series 96 User Manual
Page 35

Active if Propband 2 (PID 2
Menu) is not set to
[```0],
Burst 2 (PID 2 Menu) is set to
[``no], output 2 is not a pro-
cess (not 96 _ _ - _ F _ _-_ _ _ _)
and Operations Page Lock
(Lockout Menu) is not set to
[hide].
516 r/w
Relay: 10.0
(100)
Solid-state:
1.0 (10)
Relay: 5.0 to 60.0 (50 to
600)
Solid-state: 0.1 to 60.0
(1 to 600)
[Ct`2] Cycle Time 2
Set the cycle time in
seconds for output 2.
Active if Propband 2 (PID 2
Menu) is not set to
[```0], and
Operations Page Lock (Lockout
Menu) is not set to
[hide], and
if Output 2 is equipped for a
solid-state relay (96A _-K _ _ _-
_ _ _ _) or switched dc (96A _-C
_ _ _-_ _ _ _) or voltage power
supply option (96A _-_ _ _ _-_ _
_ _.)
519 r/w
[``no] (0)
[``no] no (0)
[`Yes] yes (1)
[brs2] Burst 2
Select burst fire
mode for output 2.
Active if Propband 2 (PID 2
Menu) is not set to
[```0],
Units Type (Global Menu) is set
to
[``US] and Operations Page
Lock (Lockout Menu) is not set
to
[hide].
514 r/w
0.00 (0)
0.00 to 9.99 minutes
(0 to 999)
[rA`2] Rate 2
Set the rate time in
minutes for output
2.
Active if Propband 2 (PID 2
Menu) is not set to
[```0],
Units Type (Global Menu) is set
to
[``S1] and Operations Page
Lock (Lockout Menu) is not set
to
[hide].
513 r/w
0.00 (0)
0.00 to 9.99 minutes
(0 to 999)
[dE`2] Derivative 2
Set the derivative
time in minutes for
output 2.
Active if Propband 2 (PID 2
Menu) is not set to
[```0],
Units Type (Global Menu) is set
to
[``US] and Operations Page
Lock (Lockout Menu) is not set
to
[hide].
512 r/w
0.00 (0)
0.00 to 99.99 repeats
per minute (0 to 999)
[rE`2] Reset 2
Set the reset time in
repeats/minutes for
output 2.
Active if Propband 2 (PID 2
Menu) is not set to
[```0],
Units Type (Global Menu) is set
to
[``S1] and Operations Page
Lock (Lockout Menu) is not set
to
[hide].
511 r/w
0.00 (0)
0.00 to 99.99 minutes
per repeat (0 to 9999)
[It`2] Integral 2
Set the integral time
in minutes for out-
put 2.
Active if one output is set to heat
and the other to cool and Oper-
ations Page Lock (Lockout
Menu) is not set to
[hide] and
Heat-Cool Mode.
510 r/w
25°F, 14°C
0° to 9999°
If
[Pb`2] is set to 0 op-
erates in on/off mode.
[Pb`2] Propband 2
Set the proportional
band for output 2.
[PiD2]
PID 2 Menu
[Oper] Operations Page
Wa t l o w S e r i e s 9 6
P a r a m e t e r s
■
6 . 5
Operations Page / PID 2 Menu
Display
Parameter
Range
Default
Modbus
Conditions for
(Modbus Value)
Register
Parameters to Appear
read/write
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.