Operations page / alarm menu – Watlow Series 96 User Manual

Page 36

background image

NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.

Active if Output 3 (Output 3

Menu) is

[``AL] (Alarm),

Alarm Sides 3 (Output 3 Menu)
is not

[``hi], output 3 is pre-

sent (96 _ _-_ _ D _-_ _ _ _) and
Operations Page Lock (Lockout
Menu) is not set to

[hide]

.

340 r/w

Process: low

limit of se-
lected sen-
sor range

Deviation:

-999

Process: low limit of se-

lected sensor range
to Alarm 3 High-1

Deviation: -1999 to 0

[A3Lo] Alarm 3 Low

Set the low alarm
set point for output
3.

Active if Output 2 (Output 2

Menu) is set to

[``AL] (Alarm),

Alarm Active Sides 2 (Output 2
Menu) is not set to

[``lo], out-

put 2 is present, but is not a
process (not 96 _ _-_ A _ _-_ _ _
_ or 96 _ _-_ F_ _-_ _ _ _) and
Operations Page Lock (Lockout
Menu) is not set to

[hide].

322 r/w

Process: high

limit of se-
lected sen-
sor range

Deviation:

999

Process: Alarm 2

Low+1 to high limit
of selected sensor
range

Deviation: 0 to 9999

[A2hi] Alarm 2 High

Set the high alarm
set point for output
2.

Active if Output 2 (Output 2

Menu) is set to

[``AL] (Alarm),

Alarm Active Sides 2 (Output 2
Menu) is not set to

[``hi], out-

put 2 is present, but is not a
process output (not 96 _ _-_ A _
_-_ _ _ _ or 96 _ _-_ F_ _-_ _ _ _)
and Operations Page Lock
(Lockout Menu) is not set to
[hide].

321 r/w

Process: low

limit of se-
lected sen-
sor range

Deviation:

-999

Process: low limit of se-

lected sensor range
to Alarm 2 High-1

Deviation: -1999 to 0

[A2Lo] Alarm 2 Low

Set the low alarm
set point for output
2.

[Alm]

Alarm Menu

[Oper] Operations Page

Active if output 2 is present (not

96 _ _-_ A _ _-_ _ _ _), one out-
put is set to

[heat], another is

set to

[COOL] and Operations

Page Lock (Lockout Menu) is
not set to

[hide].

515 r/w

0 (0)

0 to 9999

[db`2] Dead Band 2

Set point shift for
output 2 control.

Active if Output 2 is present, but

output 2 is not a process type
(not 96 _ _-_ A _ _-_ _ _ _ or 96
_ _-_ F_ _-_ _ _ _), or Output 2
(Output 2 Menu) is set to
[hEAt] or [COOL] (opposite of
Output 1

[hEAt] or [COOL] se-

lection); and Propband 2 (PID
2 Menu) is set to

[```0] and

Setup Page Lock (Lockout
Menu) is not set to

[hide].

517 r/w

3°F, 2°C

1 to 9999

[hys2] Hysteresis 2

Sets the switching
hysteresis for output
2.

6 . 6

P a r a m e t e r s

Wa t l o w S e r i e s 9 6

Operations Page / Alarm Menu

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Register

Parameters to Appear

read/write