Factor y page / diagnostics menu – Watlow Series 96 User Manual
Page 51
![background image](/manuals/359231/51/background.png)
Active: Always
1707 r
none
-199.9 to 199.9
(-1999 to 1999)
[hres] High Resolution
Displays high reso-
lution input value.
Active: Must be in
[dIag]
mode
1513 r/w
[`OFF] (0)
[`OFF] turn off the
cyclic display test (0)
[``on] turn on the
cyclic display test (1)
[DISP] Test Display
Test the indicator
lights on the front
panel.
Active: Must be in
[dIag]
mode
1514 r/w
[none] (0)
[none] none (0)
[out1] output 1 (1)
[out2] output 2 (2)
[out3] output 3 (3)
[out4] output 4 (4)
[`all] all outputs (5)
[tout] Test Output
Turns on specific
output.
Active: Always
19 r
(0)
[none] none (0)
[reLy] relay (1)
[Proc] process (4)
[`485] (6)
[`232] (7)
[OTY4] Output 4
Hardware
Read the output 4
hardware type.
Active: Always
18 r
(0)
[none] none (0)
[reLy] relay (1)
[OTY3] Output 3
Hardware
Read the output 3
hardware type.
Active: Always
17 r
(0)
[none] none (0)
[reLy] relay (1)
[`Ssr] solid-state
relay (2)
[``dc] dc (3)
[Proc] process (4)
[OTY2] Output 2
Hardware
Read the output 2
hardware type.
Active: Always
16 r
(0)
[none] none (0)
[reLy] relay (1)
[`Ssr] solid-state
relay (2)
[``dc] dc (3)
[Proc] process (4)
[OTY1] Output 1
Hardware
Read the output 1
hardware type.
Active: Always
9 r
(0)
[nonE] none (0)
[PrEt] process event
(5)
[ItY2] Input 2 Hardware
Enabled
Read the input 2
hardware type.
Active: Always
4 r
none
0.00 to 99.99
[`reu] Software Revision
Read software revi-
sion number.
Display
Parameter
Range
Default
Modbus
Conditions for
(Modbus Value)
Register
Parameters to Appear
read/write
Wa t l o w S e r i e s 9 6
P a r a m e t e r s
■
6 . 2 1
Factor
y Page / Diagnostics Menu
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.