Operations page / pid 1 menu – Watlow Series 96 User Manual
Page 33
Active if Propband 1(PID 1 Menu)
is not set to
[```0], Units Type
(Global Menu) is set to
[``US]
and Operations Page Lock
(Lockout Menu) is not set to
[hide].
502 r/w
0.00 (0)
0.00 to 99.99 repeats
per minute
[rE`1] Reset 1
Set the reset time in
repeats/minute for
output 1.
Active if Propband 1(PID 1 Menu)
is not set to
[```0], Units Type
(Global Menu) is set to
[``SI]
and Operations Page Lock
(Lockout Menu) is not set to
[hide]
.
501 r/w
0.00 (0)
0.00 to 99.99 minutes
per repeat
[It`1] Integral 1
Set the integral time
in minutes for out-
put 1.
Active if Operations Page Lock
(Lockout Menu) is not set to
[hide]
.
500 r/w
25°F, 14°C
0° to 9999°
If
[Pb`1] is set to 0 op-
erates in on/off mode.
[Pb`1] Propband 1
Set the proportional
band for PID con-
trol.
[Pid1]
PID 1 Menu
[Oper] Operations Page
Active if Operations Page (Lock-
out Menu) is not set to
[hide]
.
605 r/w
0
-1999 to 9999
[CAL1] Calibration Offset
Set the input 1 cali-
bration offset.
Active if Input 2 (Input 2 Menu)
is not set to
[`Off], Input 2 is
not set to
[E`In] (event input)
and Operations Page Lock
(Lockout Menu) is not set to
[hide]
.
316 r/w
[```L] (0)
[```L] local (0)
[~~~r] remote (1)
[`L-r] Local or Remote
Mode**
Set the mode to local
or remote set point.
Active if output 2 is present (not
96 _ _-_ A _ _-_ _ _ _), both Out-
put 1 (Output 1 Menu) and
Output 2 (Output 2 Menu) are
set to either
[heat] or [COOL]
and Operations Page Lock
(Lockout Menu) is not set to
[hide].
319 r/w
75°F, 24°C
Range Low 1 to Range
High 1
[`SP2] Set Point 2**
Set the boost set
point.
Active if Input 2 (Input 2 Menu)
is set to
[e`In] (event input),
[E`Fn] is set to [``SP], and
Operations Page Lock (Lockout
Menu) is not set to
[hide].
306 r/w
75°F, 24°C
Range Low 1 to Range
High 1
[E`SP] Event Set Point2**
Set the set point
when the event
input is active as de-
fined by Event Con-
dition.
Active if Operations Page Lock
(Lockout Menu) is not set to
[hide].
304 r/w
90
50 to 150
[AtSP] Auto-tune Set
Point
Set the auto-tune set
point as a percent of
the currently active
set point.
Display
Parameter
Range
Default
Modbus
Conditions for
(Modbus Value)
Register
Parameters to Appear
read/write
Wa t l o w S e r i e s 9 6
P a r a m e t e r s
■
6 . 3
Operations Page / PID 1 Menu
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.