Setup page / output 3 menu – Watlow Series 96 User Manual
Page 43
Active if output 3 is present (96 _
_-_ _ D _-_ _ _ _), Output 3
(Output 3 Menu) is set to
[``AL] (Alarm) and Setup
Page Lock (Lockout Menu) is
not set to
[hide].
740 r/w
[both] (0)
[both] both (0)
[``hi] high (1)
[``lo] low (2)
[Sid3] Alarm Active
Sides 3
Select alarm 3 side
option.
Active if output 3 is present (96 _
_-_ _ D _-_ _ _ _), Output 3
(Output 3 Menu) is set to
[``AL] (Alarm) and Setup
Page Lock (Lockout Menu) is
not set to
[hide].
739 r/w
[``no] (0)
[``no] no action (0)
[`yes] silence 3 en-
abled (1)
[SIL3] Silencing 3
Enable Silence 3.
Active if output 3 is present (96 _
_-_ _ D _-_ _ _ _), Output 3
(Output 3 Menu) is set to
[``AL] (Alarm) and Setup
Page Lock (Lockout Menu) is
not set to
[hide].
738 r/w
[``no] (0)
[``no] no action (0)
[`Yes] latching en-
abled (1)
[Lat3] Latching 3
Enable Alarm 3
Latching.
Active if output 3 is present (96 _
_-_ _ D _-_ _ _ __), Output 3
(Output 3 Menu) is set to
[``AL] (Alarm) and Setup Page
Lock (Lockout Menu) is not set
to
[hide].
737 r/w
3°F, 2°C
1 to 9999
[ahy3] Alarm Hysteresis 3
Set the switching
hysteresis for the
alarm output. This
defines a band on
the inside of the
alarm set point.
When the process
temperature is in
this band, the alarm
state will not
change.
Active if output 3 present (96 _ _-
_ _ D _-_ _ _ __), Output 3
(Output 3 Menu) is set to
[``AL] (Alarm) and Setup
Page Lock (Lockout Menu) is
not set to
[hide].
736 r/w
[Proc] (0)
[Proc] process alarm
(0)
[``de] deviation alarm
(1)
[Aty3] Alarm 3 Type
Select alarm 3 type.
Active if output 3 present (96 _ _-
_ _ D _-_ _ _ _), Output 3 (Out-
put 3 Menu) is set to
[``AL]
(Alarm) and Setup Page Lock
(Lockout Menu) is not set to
[hide].
*Event output is added if ramp-
ing version of the controller is
selected (96__-____-AA__.)
734 r/w
[`OFF] (0)
[`OFF] off (0)
[``AL] alarm (1)
[eunt] event (2)*
[Ot`3] Output 3
Select type of output
3.
[Out3]
Output 3 Menu
[`set] Setup Page
Wa t l o w S e r i e s 9 6
P a r a m e t e r s
■
6 . 1 3
Setup Page / Output 3 Menu
Display
Parameter
Range
Default
Modbus
Conditions for
(Modbus Value)
Register
Parameters to Appear
read/write
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.