Ia net, Xsel-r/s – IAI America XSEL-S User Manual

Page 59

background image

Chapter 3 Operation (Construction for Network)

53

IA Net

XSEL-R/S

2) Port Assignment Settings

No.

Parameter Name

(I/O parameters)

Initial Value

(Reference)

Input Range

Remarks

1 I/O Port Allocation Type

1

0 to 1

0 : Fixed Allocation (recommended)

1 : Automatic Allocation

The priority in order for extension input

and output ports assignment at automatic

assignment is as shown below:

1) Network I/F Module 2

2) Extension I/O Unit

3) IA Net (for communication among

controllers)

Assignment is applied to extension input

and output ports.

Input Ports No.1000 to 3999

Output Port No.4000 to 6999

691

Extension Input Port Start

Number at IA Net Fixed

Assignment

-1

-1 to 3999

1000+(Multiples of 16)

(Setting is invalid if set to -1)

692

Extension Output Port Start

Number at IA Net Fixed

Assignment

-1

-1 to 6999

4000+(Multiples of 16)

(Setting is invalid if set to -1)

When 1 (Automatic Assignment) is set in I/O Parameter No.1, the extension input and output

ports are assigned from the smaller number in the order described below:

4) Number of used ports in Network I/F Module 2 (CC-Link, DeviceNet, etc.)

5) Number of used ports in the Extension I/O Unit

6) Number of used ports in IA Net (for I/O communication among controllers)

When 0 (fixed assignment) is set in I/O Parameter No.1, set the assignment start port number

for each of input and output to I/O Parameters No.691 and 692. Set to -1 (invalid) to the slots

not to be used.

Note It is recommended to set to 0 (Fixed Assignment) in I/O Parameter No. 1.

Caution 1) For output ports, every 64 points require to occupy one station each.

2) When using only the input ports, it is necessary to occupy one station no

matter of the number of slots.

3) The number of stations that can be occupied by one unit of XSEL controller on

the IA Net network is four at the maximum. When using together with

communication among controllers, be careful not to exceed four stations.

(Number of stations used for I/O communication among controllers + Number

of stations used for extension I/O units ” 4)

If the number of used stations exceeds four, “560: Number of IA Net Occupied

Station Exceeded Error” will be generated.