(2) Cable Wiring 
Ɣ Use our company’s genuine cables for connecting between the actuator 
and controller, and for the teaching tool.
Ɣ Do not scratch on the cable. Do not bend it forcibly. Do not pull it. Do not
coil it around. Do not insert it. Do not put any heavy thing on it. Failure to 
do so may cause a fire, electric shock or malfunction due to leakage or 
continuity error. 
Ɣ Perform the wiring for the product, after turning OFF the power to the unit,
so that there is no wiring error.
Ɣ When the direct current power (+24V) is connected, take the great care of
the directions of positive and negative poles. If the connection direction is 
not correct, it might cause a fire, product breakdown or malfunction. 
Ɣ Connect the cable connector securely so that there is no disconnection or
looseness. Failure to do so may cause a fire, electric shock or malfunction 
of the product. 
Ɣ Never cut and/or reconnect the cables supplied with the product for the
purpose of extending or shortening the cable length. Failure to do so may 
cause the product to malfunction or cause fire. 
4 Installation
and Start
(3) Grounding 
Ɣ The grounding operation should be performed to prevent an electric shock 
or electrostatic charge, enhance the noise-resistance ability and control 
the unnecessary electromagnetic radiation. 
Ɣ For the ground terminal on the AC power cable of the controller and the
grounding plate in the control panel, make sure to use a twisted pair cable 
with wire thickness 0.5mm
2
(AWG20 or equivalent) or more for grounding
work. For security grounding, it is necessary to select an appropriate wire 
thickness suitable for the load. Perform wiring that satisfies the 
specifications (electrical equipment technical standards). 
Ɣ Perform Class D Grounding (former Class 3 Grounding with ground
resistance 100
: or below).