TECHNICAL MANUAL

Rev.

Pagine

7/52

Filling By

Checked By

03

PROFIBUS DP MODULE- DATA LINK

DESCRIPTION

Document Data

Date

Date

File name

ProfibusDP_emanual_Burkert_04.doc

19/03/08 19/03/08 19/03/08


7

The Second type of Configuration consist of 16 byte Input

With this type of Configuration it is possible exchange with only 16 the same data of the precedent

Configuration and in addition there are the values of the Totalizers positive or negative.

With the setting of a control byte, in the configuration string of the file GSD,it is possible to set the Data

Type of information returned by Input data.

The control byte is the third byte of the Configuration string (see below).
It is also possible to change the Data Type with a Class 1 and Class 2 Master and the relative Acyclic Slot

and Acyclic Index, during data exchange.

For details Acyclic Service see the relative section in this document.


The reference to the Configuration string in the GSD file is:

------------------------------------------------------------

Module = "16 Byte Input" 0x41,0x0F,0x00

2

EndModule
------------------------------------------------------------

The settings in the GSD file for to use this Configuration is:

-----------------------------------------

SlotDefinition

Slot(1) = "Process Data" 2
EndSlotDefinition

-----------------------------------------

The Configuration correspond to 16 bytes Input and the last byte indicate the Data Type selected .

Modifing the last byte in the GSD file it is possible to set the type of the Flow rate and the type of

Totalizers:

With the Configuration 0x41,0x0F,0x00 the Flow rate is in % ( 4 byte )

totalizers

positive (

4

byte

)

partial

totalizers

positive

(

4

byte

)

process flags ( 2 byte )

dynamic variations ( 1 byte )
the Data Type = 0 ( 1 byte )

-----------------------------------------------------------

Number

of

Input

byte

exchanged (

16

byte

)

With the Configuration 0x41,0x0F,0x01 the Flow rate is in % ( 4 byte )

totalizers negative ( 4 byte )
partial

totalizers

negative (

4

byte

)

process flags ( 2 byte )

dynamic variations ( 1 byte )

the Data Type = 1 ( 1 byte )

-----------------------------------------------------------

Number

of

Input

byte

exchanged (

16

byte

)

Whit the Configuration 0x41,0x0F,0x02 the Flow rate is in tecnical unit ( 4 byte )

totalizers

positive (

4

byte

)

partial totalizers positive ( 4 byte )

process flags ( 2 byte )
dynamic variations ( 1 byte )