PROFIBUS DP MODULE- DATA LINK
DESCRIPTION
Document Data
Date
Date
File name
ProfibusDP_emanual_Burkert_04.doc
19/03/08 19/03/08 19/03/08
21
bytes 6-9: (32 bit long integer, MSB first) totalizer for TOTAL volume + or batch quantity ( batch quantity
only for ML M3F )
bytes 10-13: (32 bit long integer, MSB first) totalizer for TOTAL volume - or batch quantity ( data valid
only for ML 210 )
bytes 14-15: (16 bit unsigned integer, MSB first) process flags:
bit 0 =1 if the excitation is too fast for the sensor connected
bit 1 =1 if the maximum alarm is active
bit 2 =1 if the minimum alarm is active
bit 3 =1 if the Flow rate exceeds the scale range value (overflow)
bit 4 =1 if one or more output impulses are saturated (too many impulses to emit)
bit 5 =1 if the measurement signal is highly disturbed or if the sensor is disconnected
bit 6 =1 if the measurement tube is empty
bit 7 =1 if the circuit powering the coils is not working or the sensor is disconnected
bit 8 =1 if the second measurement scale is active
bit 9 =1 if the Flow rate is lower than the cut-off threshold
bit10=1 if the Flow rate is negative
bit11=1 if a new measurement value calculated for the display is available
bit12=1 if the counter block signal is active
bit13=1 if dosing is in progress
bit14=1 if a calibration cycle is in progress
bit15=1 if a Flow rate simulation is in progress
INDEX Input = 30(dec) Static Process Data of the Flow Meter
byte 0: (8 bits integer) current INDEX Input
byte 1: (8 bits integer) current INDEX Output
bytes 2-5: (32 bit single precision IEEE floating point, MSB first) Flow rate scale range in t.u.
bytes 6-10: (5 bytes ASCII) flow rate measurement unit
byte 12: (8 bits integer) number of decimals after the point for flow rate display
INDEX Input = 31(dec) Static Process Data of the Flow Meter
byte 0: (8 bits integer) current INDEX Input
byte 1: (8 bits integer) current INDEX Output
bytes 2-4: (3 bytes ASCII) measurement unit of the counters
byte 6: (8 bits integer) number of decimals after the point for totalizers display
byte 8: (8 bits integer) measurement samples per second (Hz)
byte 20=10(dec) measurement frequency = 10 Hz
byte 20=20(dec) measurement frequency = 20 Hz
byte 20=50(dec) measurement frequency = 50 Hz
byte 20=80(dec) measurement frequency = 80 Hz
byte 20=150(dec) measurement frequency = 150 Hz
byte 20=44(dec) measurement frequency = 300 Hz
byte 20=144(dec) measurement frequency = 400 Hz
INDEX Input = 32(dec) Slave Data
byte 0: (8 bits integer) current INDEX Input
byte 1: (8 bits integer) current INDEX Output
byte 2: (8 bits integer) slave address
byte 3: (8 bits integer) pno identification number high
byte 4: (8 bits integer) pno identification number low
byte 5: (8 bits integer) DPC31 ASIC Step