Filling By

Checked By

03

PROFIBUS DP MODULE- DATA LINK

DESCRIPTION

Document Data

Date

Date

File name

ProfibusDP_emanual_Burkert_04.doc

19/03/08 19/03/08 19/03/08


34

byte 0: (8 bits integer) current INDEX Input
byte 1: (8 bits integer) current INDEX Output

bytes 2-5: (32 bit single precision IEEE floating point, MSB first) Flow rate scale range in t.u.

bytes 6-10: (5 bytes ASCII) flow rate measurement unit

bytes 12-14: (3 bytes ASCII) measurement unit of the counters

byte 16: (8 bits integer) number of decimals after the point for totalizers display

byte 17: (8 bits integer) number of decimals after the point for flow rate display

bytes 18-21: (32 bit long integer, MSB first) clock expressed in minutes starting from 01-01-1992 (only

for ML 210)

byte 22: (8 bits integer) measurement samples per second (Hz)

byte 20=10(dec) measurement frequency = 10 Hz
byte 20=20(dec) measurement frequency = 20 Hz

byte 20=50(dec) measurement frequency = 50 Hz

byte 20=80(dec) measurement frequency = 80 Hz

byte 20=150(dec) measurement frequency = 150 Hz

byte 20=44(dec) measurement frequency = 300 Hz

byte 20=144(dec) measurement frequency = 400 Hz

NOTE: The date and time are expressed with a 32 bit integer containing the number of minutes elapsed

since 01-01-1992. To calculate the date starting from this number, see the programming examples in the

section 4.0 PROGRAMMING ALGORITMS of this manual.

INDEX Input = 31(dec) Slave Data

byte 0: (8 bits integer) current INDEX Input

byte 1: (8 bits integer) current INDEX Output

byte 2: (8 bits integer) slave address

byte 3: (8 bits integer) pno identification number high

byte 4: (8 bits integer) pno identification number low
byte 5: (8 bits integer) DPC31 ASIC Step
bit 0 =1 if DPC31 B

byte 6: (8 bits integer) MAC State Offline / Passive Idle
bit 0 =1 if the MAC is in Passive Idle


byte 7: (8 bits integer) watchdog state
bit 0-1 = 00 --> Baud Search
01

-->

Baud

Control

10

-->

DP_Control

byte 8: (8 bits integer) baud rate
bit 0-3 = 0000 --> 12 MBd
0001

-->

6

MBd

0010

-->

3 MBd

0011

-->

1.5

MBd

0100

-->

500 kBd

0101

-->

187.5

kBd