Filling By

Checked By

03

PROFIBUS DP MODULE- DATA LINK

DESCRIPTION

Document Data

Date

Date

File name

ProfibusDP_emanual_Burkert_04.doc

19/03/08 19/03/08 19/03/08


33

bytes 10-13: (32 bit long integer, MSB first) totalizer for TOTAL volume - or batch quantity ( data valid
only for ML 210 )

bytes 14-15: (16 bit unsigned integer, MSB first) process flags:
bit 0 =1 if the excitation is too fast for the sensor connected

bit 1 =1 if the maximum alarm is active

bit 2 =1 if the minimum alarm is active

bit 3 =1 if the Flow rate exceeds the scale range value (overflow)
bit 4 =1 if one or more output impulses are saturated (too many impulses to emit)

bit 5 =1 if the measurement signal is highly disturbed or if the sensor is disconnected

bit 6 =1 if the measurement tube is empty

bit 7 =1 if the circuit powering the coils is not working or the sensor is disconnected

bit 8 =1 if the second measurement scale is active
bit 9 =1 if the Flow rate is lower than the cut-off threshold

bit10=1 if the Flow rate is negative

bit11=1 if a new measurement value calculated for the display is available

bit12=1 if the counter block signal is active

bit13=1 if dosing is in progress

bit14=1 if a calibration cycle is in progress
bit15=1 if a Flow rate simulation is in progress

byte 16: (8 bits integer) measurement dynamic variation as a %

INDEX Input = 14(dec) Dynamic Process Data


byte 0: (8 bits integer) current INDEX Input

byte 1: (8 bits integer) current INDEX Output

bytes 2-5: (32 bit single precision IEEE floating point, MSB first) Flow rate in t.u.

bytes 6-9: (32 bit long integer, MSB first) totalizer for TOTAL volume + or batch quantity ( batch quantity

only for ML M3F )

bytes 10-13: (32 bit long integer, MSB first) totalizer for TOTAL volume - or batch quantity ( data valid
only for ML 210 )

bytes 14-15: (16 bit unsigned integer, MSB first) process flags:
bit 0 =1 if the excitation is too fast for the sensor connected

bit 1 =1 if the maximum alarm is active

bit 2 =1 if the minimum alarm is active

bit 3 =1 if the Flow rate exceeds the scale range value (overflow)
bit 4 =1 if one or more output impulses are saturated (too many impulses to emit)

bit 5 =1 if the measurement signal is highly disturbed or if the sensor is disconnected

bit 6 =1 if the measurement tube is empty

bit 7 =1 if the circuit powering the coils is not working or the sensor is disconnected

bit 8 =1 if the second measurement scale is active

bit 9 =1 if the Flow rate is lower than the cut-off threshold
bit10=1 if the Flow rate is negative

bit11=1 if a new measurement value calculated for the display is available

bit12=1 if the counter block signal is active

bit13=1 if dosing is in progress

bit14=1 if a calibration cycle is in progress
bit15=1 if a Flow rate simulation is in progress

byte 16: (8 bits integer) measurement dynamic variation as a %

INDEX Input = 30(dec) Static Process Data of the Flow Meter