PROFIBUS DP MODULE- DATA LINK
DESCRIPTION
Document Data
Date
Date
File name
ProfibusDP_emanual_Burkert_04.doc
19/03/08 19/03/08 19/03/08
27
byte
1:
0x28
=
40(dec) index output
byte
2:
0x13
Æ Command
-----------------------------------------------------------------------------------------------------------------------------
es. Batch Commands:
byte 0: 0x28 = 40(dec) index input Æ see INDEX Input = 40(dec) Batch Data
byte
1:
0x28
=
40(dec) index output
byte
2:
0x12
Æ Command
byte
3:0x01
Æ Code Read Status
0x02
Æ Code Start Batch
0x03
Æ Code Stop Batch
0x04
Æ Code Reset the current Batch process
-----------------------------------------------------------------------------------------------------------------------------
INDEX Output = 41(dec) Setting Batch Data Memory
With this index it is possible to insert the batch data memory
byte 0: (8 bits integer) INDEX Input: the value set the type of the Input data
byte 1: (8 bits integer) INDEX Output = 40(dec)
bytes 2-3: (2 bytes 16 bit unsigned integer, MSB first) number of batch processes done for this batch
memory.
bytes 4-5: (2 bytes 16 bit unsigned integer, MSB first) value of the safety batch timer expressed in tenths of
seconds.
bytes 6-9: (4 bytes 32 bits unsigned long integer, MSB first) batch quantity value expressed in the same units
and with the same decimal digits of the volume counters.
NOTE: The recipe utilized for this configuration (16 bytes I/O) is the 00 in the meter and the name utilized
for this recipe is PROFIBUS.
es.
Insertion of the Batch Data (insertion of the data in the meter is in real time for this type of data):
byte
0:
0x28
=
40(dec) index input Æ see INDEX Input = 40(dec) Batch Data
byte
1:
0x29
=
41(dec) index output
byte
2:
0x00
byte
3:
0x00
Æ 0(dec) value for reset the counter
byte
4:
0x00
byte
5:
0x0F
Æ 15 (dec) safety batch timer
byte
6:
0x00
byte
7:
0x00
byte
8:
0x00
byte
9:
0x01
Æ 1(dec) batch quantity
---------------------------------------------------------------------------------------------------------------------------
INDEX Output = 42(dec) Setting Batch Parameters
With this index it is possible to insert the batch parameters