Figure 42 alarm variable list, Figure 42 – Panasonic 470 User Manual
Page 102
102
Chapter 6 Configuring RMON using Device Manager
Figure 42
Alarm variable list
Alarm variables are in three formats, depending on the type:
•
A chassis alarm ends in x where the x index is hard-coded. No
further information is required.
•
A card, spanning tree group (STG) or EtherStat alarm ends with
a dot (.). You must enter a card number, STG ID, IP address,
or EtherStat information.
•
A port alarm ends with no dot or index and requires using the
port shortcut menu. An example of a port alarm is ifInOctets
(interface incoming octet count).
•
For this example, select Bridge > dot1dStpTopChanges.0 from
the variable list. This example is a chassis alarm, indicated by
the ".0" in the variable.
3
For this example, select a rising value of 4 and a falling value of 0.
4
Leave the remaining fields at their default values, including a sample
type of Delta.
5
Click Insert.
If you want to make field changes, see the field descriptions shown
in
Table 44 "Rmon Insert Alarm dialog box fields" (page 103)
—End—
Nortel Ethernet Switch 460/470
Configuration — System Monitoring
NN47210-503
01.01
Standard
3.7
22 February 2007
Copyright © 2005-2007, Nortel Networks
Nortel Networks Confidential
.