Router Power Requirements

Table 31 lists the AC and DC power system electrical specifications
for J-series Services Routers.

Table 31: AC and DC Power System Electrical Specifications

Item

Specification

AC input voltage

100 to 240 VAC nominal

AC input line frequency

50 to 60 Hz

AC system current rating

J4350 Services Routers: 6 A

J6350 Services Routers: 8 A

DC input voltage

–48 to –60 VDC operating range

DC system current rating

20 A

AC Power, Connection, and Power Cord Specifications

NOTE: The AC power cord for the Services Router is intended for use with the
router only and not for any other use.

Detachable AC power cords, each 2.5 m (approximately 8 ft) long, are supplied
with the Services Router. The appliance coupler at the female end of the cord
inserts into the appliance inlet on the faceplate of the AC power supply. The
coupler is type C19 as described by International Electrotechnical Commission
(IEC) standard 60320. The plug at the male end of the power cord fits into the
power source receptacle that is standard for your geographical location.

NOTE: In North America, AC power cords must not exceed 4.5 m (approximately
14.75 ft) in. length, to comply with National Electrical Code (NEC) Sections 400-8
(NFPA 75, 5-2.2) and 210-52, and Canadian Electrical Code (CEC) Section 4-010(3).
The cords supplied with the router are in compliance.

Table 32 lists power cord specifications and Figure 28 illustrates the plug on
the AC power cord provided for each country or region.

Table 32: AC Power Cord Specifications

Country

Electrical Specifications

Plug Standards

Australia

250 VAC, 10 A, 50 Hz

AS/NZ 3112–1993

China

250 VAC, 10 A, 50 Hz

GB2099.1 1996 and GB1002 1996 (CH1-10P)

76