beautypg.com

2 setting dial function selection [p53, 2 setting dial function selection, Display operation – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 92

background image

83

2

2

.6.2

Setting dial function selection

You can use the dial like a potentiometer to perform operation.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

53

Frequency setting
operation selection

0

0, 1

0: Setting dial

frequency setting
mode

1: Setting dial

potentiometer
mode

Setting is
enabled when
Pr. 30 = "1"

Using the setting dial like a potentiometer to perform operation

POINT

Set "1" (extended function parameter valid) in Pr. 30 "extended function display
selection".
Set "1" (setting dial potentiometer mode) in Pr. 53 "frequency setting operation
selection".

Operation example

Changing the frequency from 0Hz to 60Hz during operation

Choose monitor/frequency monitor. ( key)
The inverter must be in the PU operation mode.
(Press the key.)
Pr. 30 must be set to "1".
Pr. 53 must be set to "1".

1.

PU

EXT

Mode/monitor check

RUN

PU

EXT

MODE

RUN

PU

EXT

RUN

3.

Turn the setting dial clockwise until
"60.0" appears. The flickering frequency is
the set frequency.
You need not press the key.

2.

Press the key to start the inverter.

RUN

SET

Flickers for 3s.

Display

Operation

REMARKS

If flickering "60.0" turns to "0.0", the Pr. 53 "frequency setting operation selection"

setting may not be "1".

Independently of whether the inverter is running or at a stop, the frequency can

be set by merely turning the dial.

When the frequency is changed, it will be stored as the set frequency often 10 seconds.

Refer to

(page 82).

This manual is related to the following products: