beautypg.com

MITSUBISHI ELECTRIC FR-S520 User Manual

Page 160

background image

151

Interval

Periodic*

Ar

e

a

o

f

In

spect

io

n

Inspection

Item

Description

D

a

ily

1 year

2 year

s

Method

Criterion

Instrument

Gener

al

General

(1) Check with

megger
(across
main circuit
terminals
and ground
terminal).

(2) Check for

loose screws
and bolts.

(3) Check for

overheat on
each part.

(4) Clean.

(1) Disconnect

all cables
from inverter
and measure
across
terminals R,
S, T, U, V, W
and ground
terminal with
megger.

(2) Retighten.
(3) Visual check.

(1) 5M

or

more.

(2), (3) No

fault.

500VDC
class
megger

Conductors,
cables

(1) Check

conductors
for distortion.

(2) Check cable

sheaths for
breakage.

(1), (2) Visual

check.

(1), (2) No fault.

Terminal
block

Check for
damage.

Visual check

No fault

Inverter
module

Converter
module

Check
resistance
across
terminals.

Disconnect
cables from
inverter and
measure across
terminals R, S,
T

P, N, and

across U, V,
W

P, N with a

meter with a
100

range.

Refer to page
153.

Analog
meter

Smoothing
capacitor

(1) Check for

liquid
leakage.

(2) Check for

safety valve
projection
and bulge.

(3) Measure

electrostatic
capacity.

(1), (2) Visual

check.

(3) Measure with

capacity
meter.

(1), (2) No fault.
(3) 85% or

more of
rated
capacity.

Capacity
meter

Mai

n

c

ir

c

ui

t

Relay

(1) Check for

chatter
during
operation.

(2) Check for

rough
surface on
contacts.

(1) Auditory

check.

(2) Visual check.

(1) No fault.
(2) No fault.

This manual is related to the following products: