MITSUBISHI ELECTRIC FR-S520 User Manual
Page 61
52
Func-
tion
Pa-
rame-
ter
Indica-
tion
Name
Setting Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Cus-
tomer
Setting
84 *
Multi-speed
setting (speed
12)
0 to 120Hz, - - -
0.1Hz
- - -
61
85 *
Multi-speed
setting (speed
13)
0 to 120Hz, - - -
0.1Hz
- - -
61
86 *
Multi-speed
setting (speed
14)
0 to 120Hz, - - -
0.1Hz
- - -
61
Mul
ti-
s
p
e
e
d
op
er
at
ion
fu
nc
tio
n
87 *
Multi-speed
setting (speed
15)
0 to 120Hz, - - -
0.1Hz
- - -
61
88
PID action
selection
20: PID reverse action,
21: PID forward action
1
20
101
89 *
PID
proportional
band
0.1 to 999%, - - -
0.1%
100%
101
90 *
PID integral
time
0.1 to 999s, - - -
0.1s
1s
101
91
PID upper limit 0 to 100%, - - -
0.1%
- - -
101
92
PID lower limit 0 to 100%, - - -
0.1%
- - -
101
93 *
PID action set
point for PU
operation
0 to 100%
0.01%
0%
101
PI
D c
ont
ro
l
94 *
PID differential
time
0.01 to 10s, - - -
0.01s
- - -
101
95
Rated motor
slip
0 to 50%, - - -
0.01%
- - -
109
96
Slip
compensation
time constant
0.01 to 10s
0.01s
0.5s
109
Sl
ip
c
o
m
p
ens
at
io
n
97
Constant-
output region
slip
compensation
selection
0, - - -
1
- - -
109
98
Automatic
torque boost
selection
(Motor
capacity)
0.1 to 3.7kW, - - -
(0.2 to 3.7kW, - - - for
the 400V class.)
0.01kW
- - -
109
A
u
to
m
a
tic
to
rq
u
e
bo
os
t
99
Motor primary
resistance
0 to 50
Ω
, - - -
0.01
Ω
- - -
111
Pammet
e
r Li
s
t