MITSUBISHI ELECTRIC FR-S520 User Manual
Page 31
22
Table 2 Conversion Factors for FR-S500 Series
Class
Circuit Type
Conversion Factor (Ki)
Without reactor
K31
=
3.4
With reactor (AC side)
K32
=
1.8
With reactor (DC side)
K33
=
1.8
3
3-phase bridge
(Capacitor-
smoothed)
With reactors (AC, DC sides)
K34
=
1.4
Table 3 Equivalent Capacity Limits
Received Power Voltage
Reference Capacity
6.6kV
50 kVA
22/33 kV
300 kVA
66kV or more
2000 kVA
Table 4 Harmonic Contents (Values at the fundamental current of 100%)
Reactor
5th
7th
11th
13th
17th
19th
23rd
25th
Not used
65
41
8.5
7.7
4.3
3.1
2.6
1.8
Used (AC side)
38
14.5
7.4
3.4
3.2
1.9
1.7
1.3
Used (DC side)
30
13
8.4
5.0
4.7
3.2
3.0
2.2
Used (AC, DC
sides)
28
9.1
7.2
4.1
3.2
2.4
1.6
1.4
1) Calculation of equivalent capacity (P0) of harmonic generating equipment
The "equivalent capacity" is the capacity of a 6-pulse converter converted from the
capacity of consumer's harmonic generating equipment and is calculated with the
following equation. If the sum of equivalent capacities is higher than the limit in
Table 3, harmonics must be calculated with the following procedure:
P0
=Σ
(Ki
×
Pi) [kVA]
Ki: Conversion factor (refer to Table 2)
Pi: Rated capacity of harmonic
generating equipment* [kVA]
i: Number indicating the conversion
circuit type
*Rated capacity: Determined by the
capacity of the applied motor and
found in Table 5. It should be noted
that the rated capacity used here is
used to calculate a generated
harmonic amount and is different
from the power supply capacity
required for actual inverter drive.
2) Calculation of outgoing harmonic current
Outgoing harmonic current = fundamental wave current (value converterd from
received power voltage)
×
operation ratio
×
harmonic
content
•
Operation ratio: Operation ratio = actual load factor
×
operation time ratio during
30 minutes
•
Harmonic content: Found in Table 4.