beautypg.com

MITSUBISHI ELECTRIC FR-S520 User Manual

Page 44

background image

35

1

Output waveform of terminal FM

The output signal of terminal FM has a pulse waveform as shown in the table below
and the number of its pulses is proportional to the inverter output frequency.
The output voltage (average voltage) is also proportional to the output frequency.

Terminal FM Output Voltage

Specifications

Output

waveform

Calibration parameter C1 (Pr. 900)

8V

Number

of output

pulses

(pulses/

second)

Max. 2400 pulses/s
Set a full-scale value which
achieves 1440 pulses/s.
Pr. 55: frequency monitoring

reference

Pr. 56: current monitoring

reference

Output

voltage

0 to 8VDC max. (*1)
(Approx. 5V at 1440 pulses/s)

Inverter

24V

SD

FM

FM

Example of Inverter and Frequency

Meter

*1. 0.5V or less when a DC ammeter of 300

or less internal resistance is connected

to measure the output voltage.

Adjustment

Analog meter
To adjust the reading of an analog indicator (ammeter), turn the calibration resistor
to change the current.
When using the operation panel or parameter unit for adjustment, change the pulse
width of the output waveform (calibration parameter "C1") (adjust the current through
the adjustment of the output voltage) to adjust the reading. (For details, refer to page
111.)

REMARKS

It is not recommended to use a voltage type indicator because it is easily affected
by a voltage drop, induction noise, etc. and may not provide correct reading if the
wiring distance is long.

This manual is related to the following products: