Noise reduction examples

Inverter

FR-

BIF

Sensor

Use 4-core cable for motor
power cable and use one
cable as earth cable.

Power
supply
for sensor

Use twisted pair shielded cable.

Inverter
power supply

Control
power supply

Do not earth shield but connect
it to signal common cable.

Separate inverter and power
line more than 30cm (3.94inches)
(at least 10cm (11.81inches))
from sensor circuit.

Install filter FR-BIF
on inverter's input side.

Control

box

Reduce carrier
frequency.

Motor

IM

FR-

BLF

FR-

BLF

FR-BLF

FR-BSF01

Do not earth control
box directly.

Do not earth
control cable.

FR-BLF

FR-BSF01

Install filter

on inverter's input side.

Install filter

on inverter's output side.

1

.5.8 Grounding precautions

Leakage currents flow in the inverter. To prevent an electric shock, the inverter and

motor must be grounded.

Use the dedicated ground terminal to ground the inverter. (Do not use the screw in

the casing, chassis, etc.)
Use a tinned* crimping terminal to connect the earth cable. When tightening the
screw, be careful not to break the threads.
*Plating should not include zinc.

Use the thickest possible ground cable. Use the cable whose size is equal to or

greater than that indicated in the following table, and minimize the cable length.
The grounding point should be as near as possible to the inverter.

(Unit: mm

2

)

Ground Cable Size

Motor Capacity

200V, 100V class

400V class

2.2kW (3HP) or less

2 (2.5)

2 (2.5)

3.7kW (5HP)

3.5 (4)

2 (4)

For use as a product compliant with the Low Voltage Directive, use PVC cable
whose size is indicated within parentheses.

Ground the motor on the inverter side using one cable of the 4-core cable.