3 link start mode selection [n10, 3 link start mode selection – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 140

background image

131

2

n8 (Pr. 338) "operation

command write"

0:

Computer

0:

Computer

1:

External

1:

External

Operation

location

selection

n9 (Pr. 339) "speed

command write"

0:

Computer

1:

External

0:

Computer

1:

External

Remarks

Remote setting

(RH, RM, RL)

Computer

External

Computer

External

RH, RM,

RL, REX

selection

function

15-speed selection (REX)

Pr. 59 =

"1", "2"

MRS

selection

function

PU operation interlock

(MRS)

External

External

External

External Pr. 79 = "7"

[Explanation of table]

External

: Operation is valid only from external terminal signal.

Computer

: Operation is valid only from sequence program.

Either

: Operation is valid from either of external terminal and computer.

: Operation is invalid from either of external terminal and computer.

CAUTION

When Pr. 79 "operation mode selection" is set to "7" (PU operation interlock function),

only the external terminal is made valid independently of the n8 and n9 settings

because the MRS terminal is shared.

2

.14.3

Link start mode selection

You can choose the operation mode established at power-on or at power

restoration after instantaneous power failure.

Set "1" in n10 to select the computer link operation mode.

After a link start, parameter write is enabled with a program.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

n10 (340)

Link start mode
selection

0

0, 1

Setting is enabled when Pr. 30 = "1"

The parameter number in parentheses is the one for use of the parameter unit (FR-PU04).