beautypg.com

MITSUBISHI ELECTRIC FR-S520 User Manual

Page 148

background image

139

Operation Panel Indication

OV3

FR-PU04

OV During Dec

Name

Regenerative overvoltage cut-off during deceleration or stop

Description

When the main circuit DC voltage in the inverter rises to or above
the specified value due to excessive regenerative energy during
deceleration or stop, the protective circuit is activated to stop the
inverter output. The circuit may also be activated by a surge
voltage produced in the power supply system.

Check point

Check for sudden speed reduction.

Corrective action

Increase the deceleration time. (Set the deceleration time which

matches the inertia moment of the load)

Decrease the braking duty.
Install a power factor improving reactor.

Operation Panel Indication

THM

FR-PU04

Motor Overload

Name

Motor overload cut-off (electronic thermal overcurrent protection)
(* 1)

Description

The electronic overcurrent protection in the inverter detects motor
overheat due to overload or reduced cooling capability during low-
speed operation to stop the inverter output. When a multi-pole
motor or two or more motors are run, provide a thermal relay in
the output side of the inverter.
Protection from burning due to motor temperature rise

Check point

Check the motor for use under overload.

Corrective action

Reduce the load weight.
For the constant-torque motor, change the Pr. 71 setting to the
constant-torque motor setting.

Operation Panel Indication

THT

FR-PU04

Inv. Overload

Name

Inverter overload cut-off (electronic thermal overcurrent protection)
(* 1)

Description

If a current of more than 150% of the rated output current flows
and overcurrent shut-off does not occur (200% or less), inverse-
time characteristics cause the electronic overcurrent protection to
be activated to stop the inverter output in order to protect the
output transistors.
Output transistor protection from overheat

Check point

Check the motor for use under overload.

Corrective action

Reduce the load weight.

*1. Resetting the inverter initializes the internal heat integrating data of the

electronic overcurrent protection.

Operation Panel Indication

FIN

FR-PU04

H/Sink O/Temp

Name

Fin overheat

Description

If the cooling fin overheats, the overheat sensor is actuated to
stop the inverter output.

Check point

Check for too high ambient temperature.
Check for cooling fin clogging.

Corrective action

Set the ambient temperature to within the specifications.

This manual is related to the following products: