Checking the inverter and converter modules

(1) Disconnect the external power supply cables (R, S, T) and motor cables (U, V, W).
(2) Prepare a meter. (Use 100

range.)

Change the polarity of the meter alternately at the inverter terminals R, S,
T, U, V, W, P and N, and check for continuity.

CAUTION

Before measurement, check that the smoothing capacitor is discharged.
At the time of continuity, the measured value is several to several ten's-of ohms
depending on the number of modules, number of parallel modules, circuit tester
type, etc. If all measured values are almost the same, the modules are without
fault.

Tester Polarity

Tester Polarity

Measured

Value

Measured

Value

R

P

Discontinuity

R

N

Continuity

D1

P

R

Continuity

D4

N

R

Discontinuity

S

P

Discontinuity

S

N

Continuity

D2

P

S

Continuity

D5

N

S

Discontinuity

T

P

Discontinuity

T

N

Continuity

Conv

er

te

r

modul

e

D3

P

T

Continuity

D6

N

T

Discontinuity

U

P

Discontinuity

U

N

Continuity

TR1

P

U

Continuity

TR4

N

U

Discontinuity

V

P

Discontinuity

V

N

Continuity

TR3

P

V

Continuity

TR6

N

V

Discontinuity

W

P

Discontinuity

W

N

Continuity

In

v

e

rte

r

modul

e

TR5

P

W

Continuity

TR2

N

W

Discontinuity

(Assumes the use of an analog meter.)

Converter

module

Inverter module

D1

D2

D3

D4

D5

D6

TR1

TR3

TR5

TR4

TR6

TR2

U

V

W

R

S

T

C

P

N

REMARKS

The FR-S520S-0.1K to 1.5K and FR-S510W-0.1K to 0.75K do not have T, D3 and D6.