3 european version, 1 terminal connection diagram, Inverter – MITSUBISHI ELECTRIC FR-S520 User Manual
Page 16
7
1
1
.3 European Version
1
.3.1 Terminal connection diagram
FR-S540-0.4K to 3.7K-EC(R)
Power factor improving
DC reactor
(FR-BEL: Option)
Frequency setting signals (Analog)
10 (+5V)
2
2
3
1
4 to 20mADC (+)
4 (4 to 20mADC)
Frequency
setting
potentiometer
1/2W1k
(*3)
SE
Running
Jumper: Remove this
jumper when FR-BEL
is connected.
Motor
IM
Earth
(Ground)
Alarm
output
U
V
W
P1
Selected
Operation status
output
5 (Common)
Open collector
output common
Current input (-)
Open
collector
outputs
SINK
SOURCE
Inverter
Main circuit terminal
Control circuit input terminal
Control circuit output terminal
DC 0 to 5V
DC 0 to 10V
(*2)
When using the current input as
the frequency setting signal, set
"4" in any of Pr. 60 to Pr. 63 (input
terminal function selection), assign
AU (current input selection) to any
of terminals RH, RM, RL and STR,
and turn on the AU signal.
Earth (Ground)
RS-485 Connector (*1)
AM
5
(+)
(-)
Analog signal
output
(0 to 5VDC)
B
C
A
*5
*5
*5
RUN
*5
Take care not to short
terminals PC-SD.
PC
External transistor common
24VDC power supply
Contact input common (sink)
STF
SD
Forward rotation start
Reverse rotation start
Middle
High
Low
Multi-speed selection
Contact input common
STR *4
RH
*4
RM
*4
RL
*4
Control input signals
(No voltage input allowed)
3-phase AC
power supply
NFB
L
1
MC
L
2
L
3
REMARKS
*1 Only the type with RS-485 communication function.
*2 You can switch between the sink and source logic positions. Refer to page 25.
*3 When the setting potentiometer is used frequently, use a 2W 1k
Ω
potentiometer.
*4 The terminal functions change with input terminal function selection (Pr. 60 to
Pr. 63). (Refer to page 38, 88) (RES, RL, RM, RH, RT, AU, STOP, MRS, OH,
REX, JOG, X14, X16, (STR) signal selection)
*5 The terminal functions change with output terminal function selection (Pr. 64,
Pr. 65). (Refer to page 90) (RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL,
LF, ABC signal selection)