Electrical information, C. optional accessories requirements, A. wiring requirements – Heat & Glo Fireplace XLR-PLUS-PB-AU User Manual
Page 44: B. intellifire plus™ ignition system wiring
Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU • 2264-900 Rev. o • 1/13
44
TO JUNCTION CORD
GRAY MODULE
FLAME
SENSE
IGNITER
RC100
(OPTIONAL REMOTE CONTROL)
GROUND
ORANGE
(PILOT)
GREEN
(MAIN)
BROWN
BLACK
RED
THERMOSTAT WIRE
ASSEMBLY / WALL
SWITCH WIRE
RC300 4.5V DC
(AA X 3)
JUNCTION CORD
TO OPTIONAL
COMPONENTS
TO JUNCTION
CORD 220-240 VAC
AUX300CE MODULE
240V FAN
FAN
AUX 1
AUX 2
OPTIONAL
MODULE RESET
SWITCH
WIRE ASSEMBLY
WALL SWITCH
JUMPER WIRE
C. Optional Accessories Requirements
• This appliance may be used with a wall switch, wall
mounted thermostat and/or a remote control, and module
reset switch.
Wiring for optional Hearth & Home Technologies approved
accessories should be done now to avoid reconstruction.
Follow instructions that come with those accessories.
Optional Remote Control Receiver Location
The control module and remote control receiver can be
accessed through the air space between the firebox front
and the lower-front finishing cover panel. The decora-
tive front and glass assembly must be removed to access
these components.
The IPI control module and the remote control receiver
are placed on the firebox bottom.
12
Electrical Information
A. Wiring Requirements
NOTICE: This appliance must be installed by a qualified
electrician in accordance with the relevant national and
local regulations.
• Wire the appliance junction cord to 220-240 VAC. This
is required for proper operation of the appliance.
WARNING! Risk of Shock or Explosion! DO NOT wire
220/240 VAC to the valve or to the appliance wall switch.
Incorrect wiring will damage controls.
NOTICE: The mains supply to the appliance must have
isolation of a minimum 1/8 in. (3 mm) contact separation
in both poles.
WARNING! Risk of Injury! The gas supply shall be shut
off prior to disconnecting the electrical power and remov-
ing batteries (if installed) before proceeding with any
maintenance to the appliance.
B. IntelliFire Plus™ Ignition System Wiring
• Wire the appliance junction cord to 220-240 VAC for
proper operation of the appliance.
WARNING! Risk of Shock or Explosion! DO NOT wire
IPI controlled appliance junction cord to a switched cir-
cuit. Incorrect wiring will override IPI safety lockout.
• Refer to Figure 12.1, IntelliFire Plus™ Pilot Ignition (IPI)
Wiring Diagram.
Figure 12.1 IntelliFire Plus™ Pilot Ignition (IPI) Wiring Diagram with Wall Switch or Thermostat
NOTE: 1. Ignition module, valve, pilot, and
wall switch operate on 6 volts. 220/240 VAC
is required at junction cord.
• This appliance is equipped with an IntelliFire Plus™
control valve which operates on a 6 volt system.
• For units installed in Australia, the residence’s 220/240
wall outlet to which this appliance’s power cord is con-
nected, must be wired to an in-line on/off switch. This is
required for servicing and/or resetting the control module
in the event of a control module LOCK-OUT.
• Plug the 6-volt AC power supply into the appliance junction
cord to supply power to the unit.