Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU • 2264-900 Rev. o • 1/13

16

B. Maintenance Tasks-Qualified Service

Technician

The

following tasks must be performed by a qualified ser-

vice technician.

Gasket Seal and Glass Assembly Inspection

Frequency: Annually
By: Qualified Service Technician
Tools needed: Protective gloves, drop cloth and a stable

work surface.
• Inspect gasket seal and its condition.
• Inspect fixed glass assembly for scratches and nicks that

can lead to breakage when exposed to heat.

• Confirm there is no damage to glass or glass frame.

Replace as necessary.

• Verify that fixed glass assembly is properly retained and

attachment components are intact and not damaged.

Replace as necessary.

Firebox

Frequency: Annually
By: Qualified Service Technician
Tools needed: Protective gloves, sandpaper, steel wool,

cloths, mineral spirits, primer and touch-up paint.
• Inspect for paint condition, warped surfaces, corrosion

or perforation. Sand and repaint as necessary.

• Replace fireplace if firebox has been perforated.

Control Compartment and Firebox Top

Frequency: Annually
By: Qualified Service Technician
Tools needed: Protective gloves, vacuum cleaner, dust

cloths
• Vacuum and wipe out dust, cobwebs, debris or pet hair.

Use caution when cleaning these areas. Screw tips that

have penetrated the sheet metal are sharp and should

be avoided.

• Remove all foreign objects.
• Verify unobstructed air circulation.

Gas Pressure Information

Frequency: Upon initial installation and gas valve re-

placement or service.
By: Qualified Service Technician
Tools needed: Protective gloves, manometer, flashlight,

screw driver set.
• Gas pressure taps are accessible by removing the deco-

rative front and fixed glass assembly. Refer to Section

11.A for information related to the gas valve and gas

pressure settings.

Burner Ignition and Operation

Frequency: Annually
By: Qualified Service Technician
Tools needed: Protective gloves, vacuum cleaner, whisk

broom, flashlight, voltmeter, indexed drill bit set, and a

manometer.
• Verify burner is properly secured and aligned with pilot

or igniter.

• Clean off burner top, inspect for plugged ports, corrosion

or deterioration. Replace burner if necessary.

• Check for smooth lighting and ignition carryover to all

ports. Verify that there is no ignition delay.

• Inspect for lifting or other flame problems.
• Verify air shutter setting is correct. See Section 14.G for

required air shutter setting. Verify air shutter is clear of

dust and debris.

• Inspect orifice for soot, dirt and corrosion. Verify orifice

size is correct. See Service Parts List for proper orifice

sizing.

• Verify manifold and inlet pressures. Adjust regulator as

required.

• Inspect pilot flame pattern and strength. See Figure 3.1

for proper pilot flame pattern. Clean or replace orifice

spud as necessary.

• Inspect IPI flame sensing rod for soot, corrosion and

deterioration. Polish with fine steel wool or replace as

required.

• Verify that there is not a short in flame sense circuit

by checking continuity between pilot hood and flame

sensing rod. Replace pilot as necessary.

Figure 3.1 IPI Pilot Flame Pattern