K. Install Horizontal Termination Cap

WARNING! Risk of Fire! The telescoping flue section

of the termination cap MUST be used when connecting

vent.

• 1-1/2 in. (38 mm) minimum overlap of flue telescoping

section is required.

Failure to maintain overlap may cause overheating and

fire.

• Vent termination must not be recessed in the wall. Siding

may be brought to the edge of the cap base.

• Flash and seal as appropriate for siding material at

outside edges of cap.

• When installing a horizontal termination cap, follow the

cap location guidelines as prescribed by current local or

national codes and refer to Section 6 of this manual.

CAUTION! Risk of Burns! Local codes may require in-

stallation of a cap shield to prevent anything or anyone

from touching the hot cap.

Note: When using termination caps with factory-supplied heat

shield attached, no additional wall shield firestop is required on

the exterior side of a combustible wall.

Figure 10.17 Venting through the Wall

• The termination kit should pass through the wall firestops

from the exterior of the building.

• Adjust the termination cap to its final exterior position on

the building and interlock the flue sections.

WARNING! Risk of Fire! the termination cap must be

positioned so that the arrow is pointing up.
• Use a high-temperature sealant gasket to seal between

the pipe and exterior firestop.

EXTERIOR

INTERIOR

Interior

Wall Shield

Inner Flue

Rear Flue

Heat Shield

1-1/2 in.

(38 mm min.)

overlap

Outer Flue

Figure 10.18 Termination Cap

1 in. (25 mm)

7-1/2 in.

(192 mm)

MINIMUM