beautypg.com

Vent clearances and framing, A. pipe clearances to combustibles, B. wall penetration framing – Heat & Glo Fireplace XLR-PLUS-PB-AU User Manual

Page 31

background image

31

Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU • 2264-900 Rev. o • 1/13

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to

194 mm) thick.

• If wall thickness is less than 4-3/8 in. (111 mm) the existing heat shields must be

field trimmed. If wall thickness is greater than 7-5/8 in. (194 mm) a DVP-HSM-B will

be required.

2-1/2 in. (64 mm)

top clearance

1/2 in. (13 mm)

clearance

bottom & sides

1 in

(25 mm)

bottom

clearance

Heat

Shield

Wall

Shield

Firestop

Heat

Shield

WALL

3 in. (76 mm)

top clearance

1 in. (25 mm)

clearance around

vertical sections

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to

vent.

DO NOT pack insulation or other combustibles:

• Between ceiling firestops

• Between wall shield firestops

• Around vent system
Failure to keep insulation or other material away from

vent pipe may cause over heating and fire.

8

Vent Clearances and Framing

Figure 8.2 Wall Penetration

* Shows center of vent framing hole for top venting. The center of the hole

is 1 in. (25 mm) above the center of the horizontal vent pipe.

Figure 8.1 Horizontal Venting Clearances To Combustible

Materials

A*

B

48 in.

(1220 mm)

47-1/4 in

(1200 mm)

A

10 in.

(254 mm)

B

DO NOT PACK WITH

INSULATION OR

OTHER MATERIAL

10 in.

(254 mm)

B. Wall Penetration Framing

Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must

frame a hole for the wall shield firestop(s). The wall shield

firestop maintains minimum clearances and prevents cold

air infiltration.
• The opening must be framed on all four sides using the

same size framing materials as those used in the wall

construction.

• SLP pipe - A wall shield firestop must be placed on each

side of an interior wall. A minimum 1-1/2 in. (38 mm)

overlap of attached heat shields must be maintained.

• See Section 10.K. for information for regarding the in-

stallation of a horizontal termination cap.

Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncom-

bustible materials such as concrete, a hole with diameter

10 in. (254 mm) greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall

shield firestop is only required on one side and no heat

shield is necessary.

This manual is related to the following products: