6 emergency shutdown with epo, 7 auto restart, Emergency shutdown with epo – Emerson Liebert NX 10-30kVA User Manual
Page 87: Auto restart, Warning
Operating Instructions
79
9.6
Emergency Shutdown With EPO
This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The
system will turn off the rectifier, inverter and stop powering the load immediately (including the
inverter and bypass), and the battery stops charging or discharging.
If the input utility is present, the UPS’s controls will remain active; however, the output will be
turned off. To remove all power from the UPS, the external feeder breaker should be opened.
9.7
Auto Restart
When the main and bypass sources fail, the UPS draws power from the battery system to supply the
load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it
will shut down.
The UPS will automatically restart and enable output power:
• after utility power is restored
• if “Auto Recovery after EOD Enabling” is enabled
• after the “Auto Recovery after EOD Delay Time” expires (the default delay is 10 minutes)
During the auto recovery delay, the NX will be charging its batteries to provide a safety margin
for equipment shutdown if input power fails again.
If the “Auto Recovery after EOD Enabling” feature is disabled, the user must restart the system man-
ually.
9.8
Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions
Once all appropriate measures have been taken to correct the problem indicated by the alarm mes-
sage appearing on the operator control panel display, carry out this procedure to restore the UPS to
regular operation following an EPO action or for the following reasons: Inverter Overtemperature,
Cut-off Overload, Battery Overvoltage, excessive switching (BYP: XFER COUNT BLOCK), etc.
When the user confirms that the fault is cleared:
1. Press the FAULT CLEAR button to let the system exit the emergency off state.
2. Press the INVERTER ON button (10) on the right side of the operator control panel for longer
than 2 seconds.
After the EPO button is pressed, if the input utility is removed, theUPS will shut down completely.
When input utility is returned, if the rotary switch (SW1) is in either Bypass or in Normal position,
the UPS will start up on Bypass. There will be power at the output terminals of the UPS.
NOTE:
A UPS manufactured before March 2006 may first require a full power down, i.e., manual
opening of the input breakers, for the "Fault Clear" to take effect.
NOTE
The rectifier will start again, the battery contactor will close and the bypass will begin to power
the load. The Rectifier indicator (1) flashes while the rectifier is starting up. When the rectifier
enters the normal operation state (about 30 seconds), the rectifier indicator turns green.
NOTE
The rectifier will be turned on automatically when the overtemperature fault disappears at
5 minutes after the disappearance of overtemperature signals.
!
WARNING
If the rotary switch is in the Maint. position and input utility is present, there will be power at
the output terminals of the UPS.