Operating Instructions

73

9.0

O

PERATING

I

NSTRUCTIONS

9.1

NX Operating Modes

The NX can operate in any of four modes, as shown in Table 23. This section provides instructions on

switching between modes, resetting the UPS, switching the inverter On and Off and performing other

operations.
Table 23

UPS operating modes

Operating

Mode

Rotary Switch

Position

Description

Normal

Operation

NORMAL

The UPS is powering the load.

On Maintenance

Bypass

MAINT

The UPS is shut down but the load is connected to utility power via the

Maintenance Bypass Supply line.

NOTE: The load is not protected against disturbances in AC input power in this

mode.

On Test

TEST

No load power is supplied by the UPS. The load is connected to utility power

via the Maintenance Bypass Supply line.

NOTE: The load is not protected against disturbances in AC input power in this

mode.

On Static

Bypass

BYPASS

or

NORMAL

The load power is supplied through the static bypass line. This may be

considered as a temporary mode during load transfers between inverter and

maintenance bypass or supply under abnormal operating conditions.

NOTE
1. The user controls and indicators mentioned in these procedures are identified in 8.0 -

Operator Control and Display Panel.

2. The audible alarm may sound at various points during these procedures. It can be canceled

at any time by pressing the SILENCE ON/OFF push button.

NOTE
This unit refers to some modes and conditions that are set or adjusted using proprietary service

software. To take advantage of all the available features for the NX, the unit must be

commissioned by a Liebert factory-trained service engineer.