Operator Control and Display Panel

61

8.2

Mimic Display Indicators

The Mimic display on the front panel consists of six indicators arranged in a single-line diagram

depicting the various paths of UPS power, as shown in Figure 48.

Figure 48 Mimic display indicators location

The current operational status of the Liebert NX is indicated by the color of the indicators—green,

amber or red—and whether they are ON (solid), flashing or OFF. Table 18 provides a guide to inter-

preting the various states of the indicators.

Table 18

Mimic display status indicators

Indicator

(see

Figure 48)

Green

Flashing Green / Amber

Red

Off

1. Rectifier

Load on rectifier

Flashing Green: Utility normal,

but rectifier not operating

Rectifier fault

Rectifier is normal, but utility is

abnormal

2. Battery

Battery powering

the load

Flashing Green: Battery pre-

warning (low battery)

Battery or battery

converter abnormal*

Battery and converter are

normal, and battery is not

discharging

3. Bypass

Load on Bypass

power

Bypass out of

normal range

Bypass Normal

4. Inverter

Inverter powering

the load normally

Flashing Green: Inverter on

standby

Inverter fault

Inverter normal, but off

5. Load

UPS output on

UPS output

overloaded

UPS no output power

6. Status

No alarms—UPS

working normally

Amber: UPS has a general

alarm

UPS has a serious

alarm

* Battery or battery converter abnormal events include these event messages (see Table 44 in Appendix A): No Battery, Battery Replaced,

Battery Reverse, Batt. Conv. Over. Curr., Batt. Converter Fault, Batt. Converter Overtemp.

Mimic indicators
1. Rectifier indicator
2. Battery indicator
3. Bypass indicator
4. Inverter indicator
5. Load indicator
6. Status indicator

EPO

INVERTER ON

INVERTER OFF

FAULT CLEAR SILENCE ON/OFF

Liebert NX

2006-01-22

12:30:36

30KVA-3X3

Unit #1

Normal

?

Bypass

Main

Vphase V

Iphase A

Freq. Hz

Vline V

P. F.

A(AB)

120

20.5
50.1

208

0.99

B(BC)

120

20.5
50.1

208

0.99

C(CA)

120

20.5
50.1

208

0.99

F2

F4

HELP

F1

F3

Output

Input Breaker Closed 01-12 12:28:16
Manual Turn On 01-12 12:30:06
UPS in Normal Mode 01-22 12:30:16

1

2

3 4

5 6