Table 43, Distance to connection points on the nx ups – Emerson Liebert NX 10-30kVA User Manual
Page 104
Specifications and Technical Data
96
11.2 Cable Lengths: Floor to Connection Point Inside UPS
To help calculate the total cable length required, refer to Table 43 for the distance from the floor to
selected connection points inside the NX. Determine the cable length required to reach the NX, then
add the appropriate length from the table and adequate slack for repair and maintenance.
Table 43
Distance to connection points on the NX UPS
Connection Point on UPS
Distance
From
Floor
in. (mm)
From
Top of Unit
in. (mm)
Bypass AC input supply
30 (750)
30 (750)
UPS output AC
30 (750)
30 (750)
Neutral busbars—Input and Output
11 (280)
55 (1397
Battery power
16 (400)
58 (1474)
Auxiliary cables: Monitor board (U2)
60 (1500)
20 (508)
Communications
55 (1400)
25 (635)
Ground
8 (197)
56 (14227)
Parallel Board
70 (1780)
20 (508)
Use wiring rated at 75°C or greater.