Table 43, Distance to connection points on the nx ups – Emerson Liebert NX 10-30kVA User Manual

Page 104

background image

Specifications and Technical Data

96

11.2 Cable Lengths: Floor to Connection Point Inside UPS

To help calculate the total cable length required, refer to Table 43 for the distance from the floor to

selected connection points inside the NX. Determine the cable length required to reach the NX, then

add the appropriate length from the table and adequate slack for repair and maintenance.
Table 43

Distance to connection points on the NX UPS

Connection Point on UPS

Distance

From

Floor

in. (mm)

From

Top of Unit

in. (mm)

Bypass AC input supply

30 (750)

30 (750)

UPS output AC

30 (750)

30 (750)

Neutral busbars—Input and Output

11 (280)

55 (1397

Battery power

16 (400)

58 (1474)

Auxiliary cables: Monitor board (U2)

60 (1500)

20 (508)

Communications

55 (1400)

25 (635)

Ground

8 (197)

56 (14227)

Parallel Board

70 (1780)

20 (508)

Use wiring rated at 75°C or greater.