2 verify switching between operation modes, Switch from normal mode to battery mode, Switch from normal mode to bypass mode – Emerson Liebert NX 10-30kVA User Manual
Page 84: Switch from bypass mode to normal mode, Verify switching between operation modes
Operating Instructions
76
5. Turn the rotary switch to NORMAL, then press the INVERTER ON control button for 2 seconds.
The inverter will start and the inverter indicator will flash green. After the inverter is ready, the
UPS transfers from bypass to inverter, the bypass indicator turns off and the inverter and load
indicators turn on.
The UPS is operating normally. The UPS Mimic display indicators will:
9.2.2 Verify Switching Between Operation Modes
Switch from Normal Mode to Battery Mode
• Open CB1 to enter battery mode. This breaks the utility connection to the NX.
To return to normal mode, close CB1 after a few seconds. The rectifier will restart automatically
after 10 seconds and resume feeding power to the inverter.
Switch from Normal Mode to Bypass Mode
• Press INVERTER OFF button to switch to bypass mode.
Switch from Bypass Mode to Normal Mode
• Turn the rotary switch to NORMAL.
• In bypass mode, press the INVERTER ON button. When the inverter is ready, the UPS will
switch to normal mode.
Indicator
State
Rectifier indicator
Green
Battery indicator
Off
Bypass indicator
Off
Inverter indicator
Green
Output indicator
Green
Status indicator
Green
NOTE
In bypass mode, the load is being powered by the utility and is not receiving conditioned power
through the inverter.