beautypg.com

Figure 37 maintenance bypass interconnection, Table 12, Figure 37 – Emerson Liebert NX 10-30kVA User Manual

Page 58: Maintenance bypass interconnection

background image

Installation Drawings

50

Figure 37 Maintenance Bypass interconnection

Table 12

Liebert-supplied interconnect wiring for Maintenance Bypass Cabinet

Run

From

To

Conductors

A

Utility AC source

Maintenance

Ph A, B, C bypass/ transformer cabinet

B

Utility AC source

Maintenance

Neutral bypass/ transformer cabinet

C

Maintenance

UPS module AC input

Neutral - UPS Input

D

Maintenance

UPS module AC input

Ph A, B, C - UPS Input

E

UPS module AC output

Maintenance

Ph A, B, C - UPS Output

F

UPS module AC output

Maintenance

Neutral - UPS Output

G

Maintenance

Load AC connection

Neutral bypass cabinet

H

Maintenance

Load AC connection

Ph A, B, C bypass cabinet

I

Utility AC source

All ground connections

Ground

J

Monitoring terminal block

UPS Parallel Logic Board (M3)

Bypass contacts

NOTES

1. All Liebert-supplied cable must be repositioned prior to and while the cabinets are being placed in their

final installed location.

2. All interconnection hardware supplied by Liebert.
3. AC connections must be made to the UPS module before attaching maintenance bypass/transformer

cabinet to UPS module.

4. Utility AC source neutral not required for maintenance bypass/transformer cabinet types D, E, M, N.
5. All cabling will be field-supplied when maintenance bypass/transformer cabinet is configured as stand-

alone cabinet.

6. Maintenance bypass/transformer cabinets must attach to the left side only.
7. Refer to the individual drawing of each piece of equipment for additional details.

Refer to Table 12 for key to interconnection

Maintenance Bypass/Transformer Cabinet

front view without front door and panel

UPS Module

left-side view without side panel