Option Installations

36

5.3.7 Emergency Power Off (EPO)

The external emergency stop facility is identical to that described for the single-unit installation—

that an individual emergency stop button is provided for each unit.

Figure 26 Connecting EPO push button

5.4

Battery Circuit Breaker Box

The box contains the same battery isolating circuit breaker as mounted in the battery cabinet.
Two battery circuit breaker boxes are available for use in installations where the battery is not

installed in the battery cabinet, in which case the appropriate battery box is fitted as close as possible

to the battery and connected to the UPS equipment as illustrated in Figure 27.
The battery circuit breaker box, is required to protect the battery from overcurrents. It also provides

electrical isolation between the UPS and the battery, permitting technical service personnel to reduce

the risks involved in maintenance work to a minimum.
A separate safety earth must be connected between the UPS unit and circuit breaker box.
Two boxes are available depending on the UPS power rating.

The circuit breaker has the following features:

• Short-circuit protection.
• Protection against battery cabinet and ups connection errors (polarity reversal +/-).

Table 7

Available battery circuit breaker boxes

UPS

Dimensions (in)

H-W-D

Circuit Breaker

10-15 kVA

32.25x20.25x8.3

70A

20-30 kVA

32.25x20.25x8.3

125A

UPS2

UPS1

Monitor Board

Monitor Board

X2:1
X2:2

X2:1
X2:2

Normally

Closed EPO

UPS1

X2:3

X2:4

Monitor Board

UPS2

X2:3
X2:4 Monitor Board

Normally

Open EPO