beautypg.com

1 power switches, Figure 58 power switches - 10kva nx, Table 24 rotary switch configuration – Emerson Liebert NX 10-30kVA User Manual

Page 82: Power switches, Table 24, Rotary switch configuration

background image

Operating Instructions

74

9.1.1 Power Switches

The UPS can be isolated by means of power switches, mounted inside the cabinet and accessible after

opening the front door.
The location of the UPS power switches is shown in Figure 58.

Figure 58 Power switches - 10kVA NX

The UPS unit power switches are CB1 and SW1.

CB1 - Input Isolator. Connects the utility supply to the UPS input.
SW1 - Rotary switch. Has four positions—NORMAL, BYPASS, TEST and MAINT—that corre-

spond to different positions of the SW1-A/B/C/D.
The positions of the rotary switch (SW1) are:

SW1-A - Output Isolator. Connects the output of the UPS to the load.
SW1-B - Neutral Isolator. Connects neutral to the UPS.
SW1-C - Bypass Isolator. Connects the UPS with the bypass supply.
SW1-D - Maintenance Bypass Isolator. Permits supply of the load directly by the bypass

line for maintenance of the UPS unit.

The functions of the rotary switch are shown in Table 24.
Table 24

Rotary switch configuration

Rotary

switch

position

OUTPUT

(SW1-A)

BYPASS

(SW1-C)

MAINT

(SW1-D)

NEUTRAL

(SW1-B)

NORMAL

BYPASS

TEST

MAINT

NOTE
Do NOT turn the rotary switch too fast. Allow the rotary switch to stay in each position at least

three seconds before turning it to the next position.

SW1 - Rotary Switch

Inside the door, near

the center (above the

batteries)

CB1 - Utility

Connection

Inside the door,

left side