Emerson Liebert NX 10-30kVA User Manual
Page 109

UPS Status Messages
101
Battery Contactor Open
Battery Contactor Open
Battery Contactor Close
Battery Contactor Close
Battery Reverse
Connect the battery again and check the wiring of batteries
No Battery
Check the battery and the wiring of batteries
Auto start
After UPS was shutdown at EOD, inverter auto starts when utility restore.
BCB closed
BCB closed from dry contact signal.
BCB open
BCB open from dry contact signal.
Battery Float Charging
Battery is float charging
Battery Boost Charging
Battery is boost charging
Battery Discharging
Battery is discharging
Battery Period Testing
Battery is period self-testing.
Batt. Capacity Testing
Battery is capacity self-testing.
Batt. Maint. Testing
Battery is maintenance self-testing.
UPS System Testing
UPS System is testing
Inverter in Setting
Inverter is in parameter setting
Rectifier in Setting
Rectifier is in parameter setting
Balancer Fault
Internal VDC (+) and VDC (-) offset by over 50V exceeding the inverter DC offset compensation
capacity. Inverter shuts down. Load transfers to bypass.
Balancer Over Current
Internal Inverter DC offset balancing IGBT current rating exceeded 300%. Inverter shuts down.
Load transfers to bypass.
Batt. Contactor Fail
Battery contactor or circuit breaker not responding to control signals.
Batt. Converter Fault
Battery converter output voltage beyond limits or battery fuse failed. Battery converter shuts
down. Battery backup not available.
Batt. Conv. Over. Curr.
Battery converter overloaded. Battery converter shuts down. Battery backup not available.
Batt. Converter Overtemp. Overheating of battery converter heatsinks. Battery converter shuts down. Battery backup not
available.
Operation Invalid
This record is registered following an incorrect operation.
Byp. Abnormal Shutdown
Both bypass and inverter voltages unavailable. Load interruption.
Setting Save Error
History records not saved. (Reserved)
Mains Neutral Lost
AC Input mains reference neutral not detected.
Balancer overtemp.
Inverter voltage offset control choke overheated. Inverter shuts down. Load transfers to bypass.
Protocol version clash
Firmware incompatibility between monitor board and digital signal processor board.
MBP-T cabinet Fan Fault
Maintenance bypass cabinet fans fault.
Ext Input TX Overtemp
External input isolation transformer overtemperature
Ext Output TX Overtemp
External output isolation transformer overtemperature
Battery Room Alarm
Environment in Battery Room Needs Attention
Rec Flash Update
Rectifier firmware is being updated
Inv Flash Update
Inverter firmware is being updated
Monitor Flash Update
Monitor firmware is being updated
Input contactor fault
Input contactor fault
Contactor P.S. 1 fault
Contactor Power Supply board 1 Fault
Contactor P.S. 2 fault
Contactor Power Supply board 2 Fault
LBS abnormal
LBS is abnormal
DSP firmware error
The inverter firmware does not match the rectifier firmware.
Table 44
UPS status messages (continued)
Event Message
Description / Suggested Action (if any)