beautypg.com

0 installation drawings, Nstallation, Rawings – Emerson Liebert NX 10-30kVA User Manual

Page 52: 0 - installation drawings, Figure 30

background image

Installation Drawings

44

6.0

I

NSTALLATION

D

RAWINGS

The diagrams in this section illustrate the key mechanical and electrical characteristics of the NX

UPS System cabinets.

Figure 30 Dimensional view- front and left side views

1. All dimensions are in millimeters.
2. A minimum of 24 inches clearance above the unit is required for air exhaust.
3. Installation and service access required. Left-side access recommended for maximum ease of

installation.

4. Keep cabinet within 15 degrees of vertical while handling.
5. Top and bottom cable entry available through removal access plates. Remove punch to suit conduit size

and replace.

6. Unit bottom is structurally adequate for forklift handling.
7. Open door to replace air filter, washable type, size 354x314.
8. Threaded mounting holes used for seismic anchoring or floor stand. Note: If a floor stand is used, the

weight of the unit must be supported under all casters.

9. Each mounting location is supported by two 10 GA. (.135”) galvanized steel. The threaded 12mm insert

is approximately 3/4” deep. Mounting bolts must be threaded into unit.

10. Includes side panel. Refer to Detail A for dimension to frame with side panel removed. Side panels are

removed between adjacent units that are bolted together.

11. Adjustable stops are not designed to carry the full weight of the cabinet. Finger-tighten stop against the

floor, then tighten with a wrench less than two turns for friction against the floor.

Monitoring

Panel

Air intake area.

Do not block

air filter.

FRONT VIEW

LEFT SIDE VIEW

10mm dia. threaded

mounting holes

Detail “A” Rear of unit

shown without side panel

Adjustable Stops

(see Note 11)

825

600

1600

90

Leveler