Electrical Connections

16

2.3.2 Maintenance Bypass Cabinet Interface

J26 and J30 are the MBC interface.

2.3.3 BCB Box Interface

J10 is the BCB box interface.

Figure 9

Jumper connection for BCB interface

Table 2

Maintenance bypass cabinet interface

Position

Name

Description

J26.1

T_IT

1

Input transformer over temperature (N.C.)

J26.2

AUX_I

Reserved

J26.3

+12V

+12V Power

J26.4

GND

Power Ground

J30.1

FUSE

Reserved

J30.2

F_FAN

Fan Fail Alarm (N.C.)

J30.3

T_OT

1

Output Transformer Overtemperature (N.C.)

J30.4

AUX_O

Reserved

1 - Must be configured by software before becoming active

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded

for maximum runs between 82 and 197 feet (25-60m), respectively.

Table 3

BCB box interface

Position

Name

Description

J10.1

DRV

BCB Driver Signal - Reserved

J10.2

FB

BCB Contact State

J10.3

GND

Power Ground

J10.4

OL

BCB On-Line - Input - This pin will become active when

BCB interface is connected. (N.O.)

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded

for maximum runs between 82 and 197 feet (25-60m), respectively.

NOTE
If BCB interface is connected, a jumper needs to added between Pin 3 and Pin 4.

UPS Monitoring Board

J10

OL

DR

V

GN

D

FB

Battery Circuit Breaker

OL

Aux – N.O.

Aux – N.O.