3 network status, 4 pointbus status – ProSoft Technology ILX34-AENWG User Manual
Page 98
Diagnostics and Troubleshooting
ILX34-AENWG ♦ Point I/O Platform
User Manual
Wireless POINT I/O Adapter
Page 98 of 177
ProSoft Technology, Inc.
August 16, 2013
Indication
Probable Cause
Recommended Action
Flashing
Green/Off
Transmit or receive activity present.
None
Steady
Green
Link established.
None
4.6.3 Network Status
Indication
Probable Cause
Recommended Action
Off
Device not initialized. The module
does not have an IP address.
Apply power to device, verify IP address, and
correct, as needed.
Flashing
Green
No CIP connections present. Device
has an IP address, but no CIP
connections are established.
None
Solid Green
CIP connections present. Device
online and has an IP address, and
CIP connections are established.
None
Flashing Red One or more CIP connections has
timed-out.
Check for I/O module failure and controller
operation, and correct, as needed.
Solid Red
Duplicate IP address detected.
Verify IP address setting and correct, as
needed.
Flashing
Red/Green
The module is performing a self-test
(only occurs during cycle power test).
None
4.6.4 POINTBus Status
Indication
Probable Cause
Recommended Action
Off
Device not powered - check module
status indicator.
Apply power to device.
Flashing
Red/Green
LED cycle power test present.
None
Flashing Red Recoverable fault occurred:
At cycle power the number of
expected modules does not
equal the number of modules
present
Configure chassis size.
A module is missing
Check for missing module and reinstall
as needed.
Node fault (I/O connection
timeout) occurred.
Check for I/O module failure and correct
as needed.
Solid Red
Unrecoverable fault occurred - the
adapter is bus off.
1. Cycle power to device.
2. If condition persists, replace device.
Flashing
Green
Firmware (NVS) update in progress.
None
Solid Green
Adapter online with connections
established (normal operation, Run
mode).
None