4 digital 4 point input – ProSoft Technology ILX34-AENWG User Manual
Page 121
ILX34-AENWG ♦ Point I/O Platform
Ladder Logic
Wireless POINT I/O Adapter
User Manual
ProSoft Technology, Inc.
Page 121 of 177
August 16, 2013
5.2.4 Digital 4 POINT Input
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-IB4
4 POINT 10…28V dc Input, Sink
1734-IV4
4 POINT 10…28V dc Input, Source
Configuration Data
Data Type
Default Value
Valid Data Values
Filter Off On Time - POINT 0
INT
1,000
-32,768…32,767
s (see note)
(0…65,535)
Filter On Off Time - POINT 0
INT
1,000
-32,768…32,767
s (see note)
(0…65,535)
Filter Off On Time - POINT 1
INT
1,000
-32,768…32,767
s(see note)
(0…65,535)
Filter On Off Time - POINT 1
INT
1,000
-32,768…32,767
s (see note)
(0…65,535)
Filter Off On Time - POINT 2
INT
1,000
-32,768…32,767
s(see note)
(0…65,535)
Filter On Off Time - POINT 2
INT
1,000
-32,768…32,767
s(see note)
(0…65,535)
Filter Off On Time - POINT 3
INT
1,000
-32,768…32,767
s (see note)
(0…65,535)
Filter On Off Time - POINT 3
INT
1,000
-32,768…32,767
s (see note)
(0… 65,535)
Input Data
Data Type
Default Value
Valid Data Values
Input Data - POINT 0, 1, 2, 3
SINT, BIT
0
0=Off
1=On
Output Data
Data Type
Default Value
Valid Data Values
None
Note: POINT I/O Modules support the Unsigned Integer data type UINT (0 to 65,535 range).
RSLogix 5000 software supports the signed Integer data type INT (-32,768 to +32,767 range).
To enter Filter values from +32,768 to +65,535 ms, use this conversion formula:
Desired Filter Value (in ms) - 65536 = Entered Filter Value (in ms).
Example: for a 40 ms filter time, 40000 - 65536 = -25536
5.2.5 Digital 2 POINT Output - Without Diagnostic Status
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-OA2
2 POINT 120V ac Output
1734-OW2
2 POINT ac/dc Relay Output
1734-OX2
2 POINT Relay Output N.O./N.C.