Configuration Data
Data Type
Default Value
Valid Data Values
DeviceNet Record Header Mode
SINT
0
0=Transmit Handshake
1=Transmit Immediate
Transmit Data / Receive Data / Delimiter / Pad Character
Note: 7 data bits allows ASCII Character data values of 0 to 127, which RSLogix 5000 software
does support in the signed Short Integer data type SINT (-128 to +127 range).
Note that 8 data bits allows ASCII Character data values of 0 to 255.
To enter values from +128 to +255, use this conversion formula:
Desired Decimal Value - 256 = Entered Decimal Value.
Example: for an ASCII Character value of 128,
128 - 256 = -128
1734-232ASC
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-232ASC
1 Channel ASCII Interface Module
Input Data
Data Type
Default Value
Valid Data Values
Receive Record Number
SINT
0
-128…+127 (0…255)
Status
SINT
0
TX FIFO Overflow
BIT 0
0=No Error
1=TX FIFO Overflow Error
RX FIFO Overflow
BIT 1
0=No Error
1=RX FIFO Overflow Error
RX Parity Error
BIT 2
0=No Error
1=RX Parity Overflow Error
Handshake Error
BIT 6
0=No Error
1=Handshake Error
New Data Flag
BIT 7
0=No New Data
1=New Data Present
Length_Lo
SINT
20
-128…+127 (0…128)
Length_Hi
SINT
0
0 or 1
Data[128]
SINT
0
Received ASCII Message
Output Data
Data Type
Default Value
Valid Data Values
Transmit Record Number
SINT
0
-128…+127 (0…255)
Receive Record Number
SINT
0
-128…+127 (0…255)
Status
SINT
0
TX FIFO Overflow
BIT 0
0=No Error
1=TX FIFO Overflow Error
RX FIFO Overflow
BIT 1
0=No Error
1=RX FIFO Overflow Error