Input Data
Data Type
Default Value
Valid Data Values
Status Byte Channel 1
SINT
0
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange
Cold Junction Data
INT
0
-32,768…32,767
Output Data
Data Type
Default Value
Valid Data Values
None
1734-OE2C
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-OE2C
2 Channel Analog Current Output
Configuration Data
Data Type
Default Value
Valid Data Values
Fault Value Channel 0
INT
0
-32,768…32,767
Program Value Channel 0
INT
0
-32,768…32,767
Low Engineering Channel 0
INT
1,638
-32,768…32,767
High Engineering Channel 0
INT
8,191
-32,768…32,767
Low Limit Channel 0
INT
-32,768
-32,768…32,767
High Limit Channel 0
INT
32,767
-32,768…32,767
Range Type Channel 0
SINT
0
0=4…20 mA
2=0…20 mA
Fault Mode Channel 0
SINT
1
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
Idle Mode Channel 0
SINT
1
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
Limit Alarm Latch Channel 0
SINT
0
0=No Latching
1=Alarms Latch
Alarm Disable Channel 0
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Fault Value Channel 1
INT
0
-32,768…32,767
Program Value Channel 1
INT
0
-32,768…32,767
Low Engineering Channel 1
INT
1,638
-32,768…32,767
High Engineering Channel 1
INT
8,191
-32,768…32,767