ProSoft Technology ILX34-AENWG User Manual
Page 141
ILX34-AENWG ♦ Point I/O Platform
Ladder Logic
Wireless POINT I/O Adapter
User Manual
ProSoft Technology, Inc.
Page 141 of 177
August 16, 2013
Output Data
Data Type
Default Value
Valid Data Values
Output 0 Force
BIT 0
0
0=Output Off
1=Output Forced On
Output 0 Enable
BIT 1
0
0=Output Disabled
1=Output Enabled
Output 0 Electronic Fuse
BIT 2
0
0=Auto Retry
1=Latch Off
Output 0 Diagnostic Speed
BIT 3
0
0≤ 8 ms Response
1=50 ms Response
Output 1 Force
BIT 4
0
0=Output Off
1=Output Forced On
Output 1 Enable
BIT 5
0
0=Output Disabled
1=Output Enabled
Output 1 Electronic Fuse
BIT 6
0
0=Auto Retry
1=Latch Off
Output 1 Diagnostic Speed
BIT 7
0
0≤ 8 ms Response
1=50 ms Response
1734-IJ, 1734-IK
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-IJ
1 Channel 5V dc Encoder / Counter
1734-IK
1 Channel 15…24V dc Encoder / Counter
Configuration Data
Data Type
Default Value
Valid Data Values
Counter Config
SINT
0
Config_0
Config_1
Config_2
Config_3
BIT 0
BIT 1
BIT 2
BIT 3
0000=0=Counter
0001=1=Encoder X1
0010=2=Encoder X2
0100=4=Encoder X4
0101=5=Period/Rate
0111=7=Rate Measurement
Mode_4
Mode_5
Mode_6
BIT 4
BIT 5
BIT 6
000=Store Count Disable
001=Store/Continue
010=Store/Wait/Resume
011=Store,Reset/Wait/Start
100=Store,Reset/Start
Z Input
BIT 7
0=Z Input Not Inverted
1=Z Input Is Inverted
Filter
SINT
120
(0x78H)
Filter_0
Filter_1
Filter_2
Filter_3
BIT 0
BIT 1
BIT 2
BIT 3
0000=No Filter
0001=50 kHz
0010=5 kHz
0100=500 Hz
1000=50 Hz