ProSoft Technology ILX34-AENWG User Manual
Page 146
Ladder Logic
ILX34-AENWG ♦ Point I/O Platform
User Manual
Wireless POINT I/O Adapter
Page 146 of 177
ProSoft Technology, Inc.
August 16, 2013
Example: for a 40,000 count sensor, 40000 - 65536 = -25536
Sensor Cycle
To enter Cycle values from +32,768 to +65,535, use this conversion formula:
Desired Cycle Value - 65536 = Entered Cycle Value.
Example: for 50,000 sensor cycle rotations, 50000 - 65536 = -15536
Compare 0,1 Value
To enter Compare values from +2,147,483,647 to +4,294,967,295, use this
conversion formula:
Desired Compare Value - 4,294,967,296 = Entered Compare Value.
Example: for a 3,000,000,000 compare value,
3,000,000,000 - 4,294,967,296 = -1,294,967,296
1734-SSI
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-SSI
1 Channel Synchronous Serial Interface
Input Data
Data Type
Default Value
Valid Data Values
Present Data
DINT
0
-2,147,483,648…2,147,483,647
(0…4,294,967,295)
Latched Data
DINT
0
-2,147,483,648…2,147,483,647
(0…4,294,967,295)
Status
INT
0
Input Status
BIT 0
0=Input is Off
1=Input is On
Run
BIT 1
0=Module is not Running
1=Module is Running
Decreasing Count
BIT 2
0=Count not Decreasing
1=Count is Decreasing
Increasing Count
BIT 3
0=Count not Increasing
1=Count is Increasing
Compare0 Reached
Compare1 Reached
BIT 4
BIT 5
0=Compare not Reached
1=Compare was Reached
Compare0 Status
Compare1 Status
BIT 6
BIT 7
0=Compare Off
1=Compare On
Power Fault
BIT 8
0=No 24Vdc Power Fault
1=24Vdc Power Fault
Configuration Fault
BIT 9
0=No FPGA Config Fault
1=FPGA Config data bad
Communication Fault
BIT 10
0=No FPGA Comm Fault
1=FPGA Comm Fault
Input Data Fault
BIT 11
0=No Input Data Fault
1=Input Power Fault (short)
Data Latched
BIT 12
0=Input Data Not Latched
1=Input Data Latched